Packet Communication
Accura 7500 has the following Modbus functions.
Function 03: Read Holding Registers
To read the relay
’s
parameter values, the master sends the slave device a Read Holding Registers
request packet. The Read Holding Registers request packet specifies the starting address of the
Holding Register and the word count of the registers to read.
Starting Address is a relative address in Modbus holding register 40000 [40001=0, 40002=1,
40101= 100, etc.]. Refer to Appendix B for CRC generation.
The relay responds to a packet including the value of the register requested.
Request
Slave
Function
Starting address
Word count
Error check
03
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Example]
The relay 1 sends data on A phase voltage
[
address 40101
]
and B phase voltage
[
address 40102
]
in the following code
via the
Function 03 command.
Slave address = 1, starting address = 64, word count = 2, crc high = 85, crc low = D4
Slave
Function
Starting Address
Word Count
Error Check
01
03
00
64
00
02
85
D4
Response
Slave
Function
Byte Count
Data Word 1
---
Data Word N
Error Check
03
---
1 byte
1 byte
1 byte
2 bytes
---
2 bytes
2 bytes
Data word indicates the data required in the request packet.
Example]
The Slave device 1 provides data on A phase voltage(1A1B) and B phase voltage(223B).
Slave address = 1, byte count = 4, crc high = D4, crc low = 5F
Slave
Function
Byte Count
Data Word 1
Data Word N
Error Check
01
03
04
1A
1B
22
3B
D4
5F