Page 50
UVR section
Address
Attribute
Measurement
Format
Descriptions
Definite time UVR
43261
R/W
Function
UINT16
Refer to “Value Table T9”
43262
R/W
Tap (Pickup value)
UINT16
20 - 220 / 1 V
43263
R/W
Delay
S2 UINT16 0.03 - 60.00 / 0.01 sec
43264
R/W
Reset Time Delay
UINT16
1 - 600 / 1 sec
43265
R/W
Reserved
UINT16
43266
R/W
Reserved
UINT16
43267
R/W
Reserved
UINT16
Other UVR
43268
R/W
Fault Phase Condition
UINT16
0x0000 = CB_OFF(OR)
0x0001 = CB_OFF(AND)
0x0002 = CB_ON(OR)
0x0003 = CB_ON(AND)
43269
R/W
Minimum Voltage
UINT16
0 - 50 / 1 V
43270
R/W
UVR Save Request
(Save Address : 43261 - 43269, 43271-
43278)
UINT16
0x00FF = Save Request
0x0000 = Not Save
Definite time UVR2
43271
R/W
Function
UINT16
Refer to “Value Table T9”
43272
R/W
Tap (Pickup value)
UINT16
20 - 220 / 1 V
43273
R/W
Delay
S2 UINT16 0.03 - 60.00 / 0.01 sec
43274
R/W
Reset Time Delay
UINT16
1 - 600 / 1 sec
Definite time UVR 3
43275
R/W
Function
UINT16
Refer to “Value Table T9”
43276
R/W
Tap (Pickup value)
UINT16
20 - 220 / 1 V
43277
R/W
Delay
S2 UINT16 0.03 - 60.00 / 0.01 sec
43278
R/W
Reset Time Delay
UINT16
1 - 600 / 1 sec
•••
Invalid
UINT16
•••
43280
Invalid
UINT16
POR section
Address
Attribute
Measurement
Format
Descriptions
Definite time POR
43281
R/W
Function
UINT16
Refer to “Value Table T9”
43282
R/W
Tap (Pickup value)
UINT16
5 - 100 / 1 %
43283
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
43284
R/W
POR Save Request
(Save Address : 43281 - 43283)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
•••
Invalid
UINT16
•••
43290
Invalid
UINT16