THD, K Factor
Address
Attribute
Measurement
Format
Scale
†
Descriptions
40148
R
THD of Voltage a
UINT16
x0.1
40149
R
THD of Voltage b
UINT16
x0.1
40150
R
THD of Voltage c
UINT16
x0.1
40151
R
THD of Current a
UINT16
x0.1
40152
R
THD of Current b
UINT16
x0.1
40153
R
THD of Current c
UINT16
x0.1
40154
R
K Factor of Current a
UINT16
x0.01
40155
R
K Factor of Current b
UINT16
x0.01
40156
R
K Factor of Current c
UINT16
x0.01
†
Refer to
“
Measurement Value Calculation
”
Extra energy section
Address
Attribute
Measurement
Format
Scale
†
Descriptions
40157-
40158
R/W
kWh received
1
UINT32
x1
Data Format
40159-
40160
R/W
kWh delivered
2
UINT32
x1
Data Format
40161-
40162
R
kWh total
3
[kWh re kWh delivered]
UINT32
x1
Data Format
40163-
40164
R/W
kAVRh received
UINT32
x1
Data Format
40165-
40166
R/W
kAVRh delivered
UINT32
x1
Data Format
40167-
40168
R
kAVRh total
[kAVRh re kAVRh delivered]
UINT32
x1
Data Format
•••
Invalid
UINT16
•••
40300
Invalid
UINT16
†
Refer to
“
Measurement Value Calculation
”
1
kWh/kVARh total indicates the value obtained by adding Delivered energy to Received energy.
2
kWh/kVARh delivered is positive for “view as generator”.
3
kWh/kVARh total[kWh/kVARh re kWh/kVARh delivered].
Summary of Contents for ACCURA 7500
Page 6: ...Page 6 Standard Compliance Process Control Equipment E324900...
Page 75: ......