Page 63
T11 : Digital Input Setup
Value
Descriptions
0x0000
None
0x0001
DIN 1
0x0002
DIN 2
0x0003
DIN 3
0x0004
DIN 4
0x0005
DIN 5
0x0006
DIN 6
0x0007
DIN 7
0x0008
DIN 8
0x0009
DIN 9
0x0010
DIN 10
T12 : DOUT Relay Type Setup
Value
Descriptions
0x0000
Self-resetting
0x0001
Pulsed
0x0002
Flickering
T13 : OCR, OCGR Relay Curve Setup
Value
Descriptions
0x0000
IEC A(SI) (IEC Curve A)
0x0001
IEC B(VI) (IEC Curve B)
0x0002
IEC C(EI) (IEC Curve C)
0x0003
KEPCO NI (KEPCO Normal Inverse)
0x0004
KEPCO VI (KEPCO Very Inverse)
0x0005
IEC LI
T14 : Fault, Pickup Status 1
Value
Descriptions
0x0000
None
Bit 0 = High[1]
Inverse OCR[51P]
Bit 1 = High[1]
Instantaneous, Definite time OCR[50P, 51P]
Bit 2 = High[1]
Reserved (In F/W Version 5.0 or lower, it is Instantaneous OCR)
Bit 3 = High[1]
Inverse OCGR[51G]
Bit 4 = High[1]
Definite time OCGR[51G]
Bit 5 = High[1]
Instantaneous OCGR[50G]
Bit 6 = High[1]
Definite time OVR[59P]
Bit 7 = High[1]
Instantaneous OVR[59P]
Bit 8 = High[1]
Instantaneous, Definite time UVR[27P]
Bit 9 = High[1]
Reserved (In F/W Version 4.0 or lower, it is Instantaneous UVR)
Bit 10 = High[1]
Definite time POR[47P]
Summary of Contents for ACCURA 7500