Installation
WallPod Intelligent EV Charging Unit
EVWM-V01-R1 Installation and Operation Manual
Page
23
of
35
December 2022
Figure 14 CT Clamp Positioning
Extend the CT Cable
If required, the CT cable may be extended up to a theoretical maximum of 100m.
x
To avoid interference and reduce the loss of signal, extension cables should be as
short as possible. Extensions of 20m or less are recommended.
x
Extension cables
must
be a screened ‘Twisted Pair’. A screened twisted pair within
a CAT6 computer network cable may be used.
NOTE:
Twisted pairs within a CAT cable are indicated by their matching colours.
Do NOT use conductors of different colours, interference may be induced.