PR821-CH User Manual.doc
2018-04-05
10/29
Therefore controller can be always detected on the communication bus with the same address by
means of PR Master software.
4.1.2 Addressing during Memory Reset procedure
Software address can be configured during Memory Reset procedure – see 4.2 Memory Reset
procedure.
Note: Software address is effective only if FixedID is None.
4.1.3 Addressing by means of PR Master software
Software address can be configured by means of PR Master software. In such case connect the
controller to PC via communication interface (e.g. UT-2USB, UT-4DR) or via CPR32-NET network
controller, detect the controller and configure the address.
Note: Software address is effective only if FixedID is None.
4.2 Memory Reset procedure
Memory Reset procedure erases current settings and restores default factory settings. Additionally
Full Memory Reset enables to program new MASTER card/PIN as well as new address of the
controller. After Memory Reset procedure the controller automatically enters normal working mode.
Note: If current address of the controller is hardware type (see 4.1 Controller address) i.e. FixedID
then address selected during Memory Reset procedure is ignored.
4.2.1 Simplified Memory Reset Procedure
Simplified Memory Reset restores default settings with controller address ID=00 and enables
programming of new MASTER card.
Remove connections to CLK and DTA terminals
Connect CLK with DTA
Restart the controller (place and remove jumper on RST contacts – see fig. 5 or switch power
supply off/on) - continuous acoustic signal shall be generated
Disconnect CLK and DTA
Read any card at the reader, this will be a new MASTER card
After a few seconds the controller shall restart automatically and switch to normal mode
4.2.2 Full Memory Reset procedure
Full Memory Reset restores default settings and enables programming of new MASTER card and
controller ID address. This procedure requires connection of PRT series reader with keypad (e.g.
PRT82MF).
Remove connections to CLK and DTA terminals
Connect CLK with DTA
Restart the controller (place and remove jumper on RST contacts – see fig. 5 or switch power
supply off/on) - continuous acoustic signal shall be generated
Disconnect CLK and DTA
Connect PRT series reader with keypad (e.g. PRT82MF) to CLK and DTA lines (without switching
power supply off) and execute further steps by means of that reader.
Press the [#] key
Read any card at the reader, this will be a new MASTER card or skip this step and press only
the [#] key
Enter two digits (in range of 00 to 99) by means of keypad, this will be new ID address or skip
this step and press only the [#] key so the default ID=00 could be assigned
After a few seconds the controller shall restart automatically and switch to normal mode
After Memory Reset controller resumes its work with default factory settings and configured
address. You can then test its operation using MASTER card (if available).