1.1 This manual
This manual contains minimum information that is necessary to properly install CPR32-NET network
controller within RACS 4 access control system. Full functional description of RACS 4 system and PR
Master software is specified in following documents, which are available at
www.roger.pl
:
·
PRxx2 series controllers, Functional description and programming guide
·
PRxx1 series controllers, Functional description and programming guide
·
PR Master User manual
CPR32-NET can be applied in integrations with intruder alarm panels of INTEGRA series made by
SATEL and with wireless door locks of SALLIS system made by SALTO. Both integrations are
described in dedicated documents, which are available at
www.roger.pl
.
2.
D
ESCRIPTION AND SPECIFICATION
CPR32-NET network controller is a successor to CPR32-SE network controller and it enables
enhancement of RACS 4 access control system with new functionalities. The CPR32-NET network
controllers enables:
·
events recording in central memory buffer
·
configuration of antipassback zones (Global APB) in access control system
·
concurrent arming/disarming of access controllers within particular alarm zone
·
configuration of schedules and calendars (concerns PRxx1 series controllers)
·
integration with wireless door locks of SALLIS (SALTO) system
·
integration with intruder alarm panels of INTEGRA (SATEL) series
·
time synchronization with NTP server
The network controller is equipped with two RS485 ports, which are used for communication with
access controllers and for integration with INTEGRA or SALLIS systems. The communication with
computer (PR Master software) is performed by means of Ethernet port and is secured with AES128
CBC encryption standard. Events from access control system are stored in internal memory buffer
(max. 240 000 events) or on optional memory card (30 millions events). CPR32-NET operates with
maximum number of SALLIS door locks or maximum number of Integra alarm zones based on
license, which can be purchased from Roger company.
Note: The CPR32-NET requires PR Master software in version 4.5.4 or newer.
Note: Default, free of charge licence for CPR32-NET enables operation with 2 door locks of SALLIS
system and 2 alarm zones of INTEGRA alarm panel.
Table 1. Specification
Supply voltage
Nominal 18VAC, min./max. range 17-22VAC
Nominal 12VDC, min./max. range 10-15VDC
Nominal 24VDC, min./max. range 22-26VDC
Backup battery
13.8V/7Ah, charging current app. 300mA
Current consumption
Average: 100 mA for 18VAC (excluding loads connected to AUX/TML
term.)
Inputs
Eight (IN1...IN8) NO/NC inputs, electrically biased to +12V via 5.6k
Ω
resistor, triggering level approx. 3.5V
Relay outputs
Two (REL1, REL2) relay outputs with single NO/NC contact, 30V/1.5A
Transistor outputs
Six (OUT1...OUT6) open collector transistor outputs, 15VDC/1A max. load
Power supply outputs
Two power supply outputs:12VDC/0.2A (TML) and 12VDC/1A (AUX)