PowerFlex 7000 Drive (P_PF7000)
Maintenance Tab Page 2
The following table shows the functions on the Maintenance tab Page 2.
Table 15 - Maintenance Tab Page 2 Description
Function
Action
Security
Configuration Parameters
Bumpless Program/
Operator Transition
Check to have program settings, such
as Speed Reference, track operator
settings in Operator mode, and have
operator settings track Program
Settings in Program mode.
Equipment
Maintenance
(Code C)
Cfg_SetTrack
Bumpless
Transition from
Override/Hand to
Program/Operator
Check to have the Program and
Operator Speed Reference track the
Override Speed Reference in Override
mode or the actual speed in Hand
mode.
Cfg_SetTrackOvrdHand
Time to pulse
Out_Reset to clear
drive fault (sec)
Type the amount of time to hold
Out_Reset true to reset a drive fault
when a reset command is received.
Configuration
and Tuning
Maintenance
(Code D)
Cfg_ResetPulseT
Time after Start to
get Run Feedback
before Fault (sec)
Type the amount of time to allow for
the drive’s run feedback to confirm
the drive has started before raising a
Fail to Start alarm.
Cfg_FailToStartT