PowerFlex 7000 Drive (P_PF7000)
Start & Stop
Commands -
Program keeps
Control in Operator
mode
Check to keep control of the drive Start
and Stop commands with the Program,
even if the instruction is in Operator
mode.
IMPORTANT
: The Program cannot Jog
the drive, even if Jogging is enabled.
Clear this checkbox to have control of
the drive Start, Stop, and Jog follow
Instruction mode.
Engineering
Maintenance
(Code E)
Cfg_ProgKeep.1
Forward & Reverse
Commands -
Operator keeps
Control in Program
mode
Check to keep control of the drive
Forward and Reverse commands, if
used, with the Operator, even if the
instruction is in Program mode.
Clear this checkbox to have control of
the drive Forward and Reverse
commands follow the Instruction
mode.
Cfg_OperKeep.2
Forward Reverse
Commands -
Program keeps
Control in Operator
mode
Check to keep control of the drive
Forward and Reverse commands (if
used) with the Program, even if the
instruction is in Operator mode.
Clear this checkbox to have control of
the drive Forward and Reverse
commands follow the Instruction
mode.
Cfg_ProgKeep.2
Operator ‘Stop’
command available
in any mode
Check (= 1) so that the OCmd_Stop
has priority and is accepted at any
time.
Clear this checkbox (= 0) so that the
OCmd_Stop works only in Operator or
Maintenance mode.
Cfg_OperStopPrio
Allow local ‘Start’ or
‘Stop’ without
triggering alarm
Check (= 1) to allow local start/stop
without an alarm.
Clear this checkbox (= 0) to
start/stop from the HMI or program
only.
Cfg_AllowLocal
Time to ramp speed
feedback when in
Loopback Test
(seconds)
Enter the time, in seconds, to ramp
speed feedback when in Simulation.
Cfg_SimRampT
Table 19 - Engineering Tab Page 4 Description
Function
Action
Security
Configuration Parameters