Installation location
Be sure to maintain a sufficient distance from wiring ducts, and other
machines below and above the module for proper ventilation.
Do not install the modules stacked up or horizontally. Doing so will
prevent proper cooling of the module and cause overheating inside
the PLC (programmable controller).
Do not install the module above devices which generate heat such as
heaters, transistors or large scale resistors.
In order to eliminate any effects from noise emission, power wires and
electromagnetic devices should be kept at least 100 mm away from the
surfaces of the module. When installing the module behind the doors
of the operation panel, be especially careful to maintain these
distances.
Space for programming tool connection
Leave a space of at least 180 mm from the mounting surface for
programming tool connections and wiring.
Duct
50mm or more
Duct
50mm or more
50mm or more
Duct
PLC
body
Ot
h
e
r
equ
ipments
Door of the panel
50mm or more
100mm or more
Programming
cable
Approx. 180mm
Approx. 110mm