34
Internal circuit and wiring diagram
Product name
SSR output module
Catalog number
NX-Y16SSR
Number of input points
16 points
Insulation method
SSR
Rated load voltage
100 to 240V AC
Operating load voltage range
85 to 264V AC
Max. load current
0.5A/point
OFF state leakage current
100
µ
A
or less
Response time
OFF
→
ON
1ms or less
ON
→
OFF
0.5 CYCLE + 1ms or less
Internal current consumption (5V)
250mA or less
Fuse rating
3A
Common method
8 points/1COM
Operation indicator
LED
External cable connection type
Terminal block connection (M3.5), Detachable
terminal block (20 pins)
Recommended cable size
0.5 to 1.25 mm
2
Weight
Approx. 240g
Types
(A) Type
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
VCC
AC100 to 240V
1
3
5
7
0
2
4
6
9
B
D
8
A
C
F
COM
F
COM