Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
129
Appendix
B
Catalog Number Explanation
PowerFlex 6000 Medium Voltage Variable Frequency Drives
(1) Other Nominal System Voltage Configurations can be supplied up to 13.8 kV
(contact factory).
1
Bulletin Number
Code
Description
6000G
PowerFlex 6000
2
Drive Frame Size
Code
Description
A
A-Frame (Air-cooled)
H
H-Frame (Air-cooled)
B
B-Frame (Air-cooled)
3
Service Duty
Code
Description
A
Normal Duty, 0…1000 m Altitude. Maximum 40
˚
C
Ambient, 110% overload for 1 minute every 10 minutes
C
Heavy Duty, 0…1000 m Altitude. Maximum 40
˚
C Ambient,
150% overload for 1 minute every 10 minutes
4
Drive Current Rating
Code
Description Code
Description
15
15 Amp
680
680 Amp
5
Enclosure Type
Code
Description
M
Type 1/IP31 (with door gaskets)
K
Type 1/IP42 (with door gaskets)
6
Nominal System Voltage
(1)
Code
Description
Code
Description
A
2,400V
L
7,200V
B
3,000V
P
8,320V
C
3,300V
R
10,000V
E
4,160V
S
11,000V
G
4,800V
T
11,500V
D
5,500V
M
12,000V
F
6,000V
U
12,470V
H
6,300V
V
13,200V
J
6,600V
W
13,800V
K
6,900V
–
–
7
Line Frequency
Code
Description
5
50 Hz
6
60 Hz
8
Control Voltage
Code
Description
Code
Description
AG
110V
AL
220V
–
–
AN
230V
AJ
120V
AP
240V
Position
1
2
3
4
5
6
7
8
9
10
11
12
6000G
A
A
180
M
J
6
AJ
J
HE
E
...etc.