Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
117
Chapter 5 Preventative Maintenance and Component Replacement
5. See the Electrical Drawings for reconnecting the fiber-optic wires.
Inspect the HMI
1. Verify the input and output cables and communication cables are hand-
tight.
2. Power up the HMI.
3. Verify that the HMI display is operating normally.
Replace the HMI
Connect fiber-optic wires here
(Refer to electrical drawings)
Reconnect the PLC cable
Reconnect the bottom terminal
ATTENTION:
Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device
that all circuits are voltage free. Failure to do so may result in severe burns,
injury, or death.