18
Rockwell Automation Publication 2198-RM003A-EN-P - February 2020
Chapter 2
Replacement Considerations
and
list fuse and circuit breaker selections for Ultra3000 and
Kinetix 5100 respectively.
Table 10 - Ultra3000 Drive Fuse Selection
Drive Cat. No.
Nominal
Voltage
Phase
UL Applications (Bussmann
Fuses)
IEC (non-UL)
Applications
Class J
Class CC
2098-DSD-005
230V AC
1 PH
LPJ-6SP
FNQ-R-6
—
2098-DSD-010
230V AC
1 PH
LPJ-10SP
FNQ-R-10
2098-DSD-020
230V AC
1 PH
LPJ-20SP
FNQ-R-20
2098-DSD-030
230V AC
1 PH
LPJ-30SP
FNQ-R-30
2098-DSD-075
230V AC
3 PH
LPJ-30SP
FNQ-R-30
2098-DSD-150
230V AC
3 PH
LPJ-60SP
—
2098-DSD-
xxx
230V AC
Auxiliary Input Power
LPJ-10SP
FNQ-R-10
Table 11 - Kinetix 5100 Drive Fuse and Circuit Breaker Selection
Cat. No.
Voltage (Nom) and
Phase
UL/CSA Application
IEC (non-UL/CSA) Application
Recommended Fuse
Cat. No.
Recommended Circuit
Breaker Cat. No.
DIN gG Fuses Rating
(Amps, max)
Recommended Circuit
Breaker Cat. No.
2198-E1004-ERS
120V/230V, 1 PH
KTK-R-10
1489-M2D100
10 A
1489-M2D100
230V, 3 PH
KTK-R-10
1489-M3D100
10 A
1489-M3D100
2198-E1007-ERS
120V/230V, 1 PH
KTK-R-20
1489-M2D200
20 A
1489-M2D200
230V, 3 PH
KTK-R-15
1489-M3D130
15 A
1489-M3D130
2198-E1015-ERS
120V/230V, 1 PH
KTK-R-30
1489-M2D300
30 A
1489-M2D300
230V, 3 PH
KTK-R-25
1489-M3D200
25 A
1489-M3D200
2198-E1020-ERS
120V/230V, 1 PH
LPJ-40SP
1489-M2D400
50 A
1489-M2D400
230V, 3 PH
LPJ-35SP
1489-M3D300
40 A
1489-M3D300
2198-E2030-ERS
230V, 3 PH
LPJ-50SP
1489-M3D350
60 A
1489-M3D350
2198-E2055-ERS
230V, 3 PH
LPJ-70SP
1489-M3D600
110 A
1489-M3D600
2198-E2075-ERS
230V, 3 PH
LPJ-80SP
140G-G2C3-C70
150 A
140G-G2C3-C70
2198-E2150-ERS
230V, 3 PH
LPJ-125SP
140G-G2C3-D12
225 A
140G-G2C3-D12