93
E 612
FLAME CONTROL UNIT ARREST
CODE GENERATED BY
:
Flame arrest signal.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 0 (or via DDC). If the code persists, contact
Robur TAC.
E 616
OUTLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on outlet water temperature sensor.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
E 617
COLD INLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on inlet water temperature sensor.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
E 618
CONDENSER OUTLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on condenser outlet temperature sensor
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
E 620
CONDENSER INLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on condenser inlet temperature sensor.
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
E 628
GAS SOLENOID VALVE EXCITED WHEN THE FLAME CONTROL BOX IS LOCKED
CODE GENERATED BY
:
The flame control box is locked (E 612) but the gas solenoid valve is excited. In this case the flame
control box is reset (E 612 resets)
RESET METHOD
:
Reset may be performed via S61 board, menu 2, Parameter 1 (or via DDC). If the code persists, contact
Robur TAC.
U
629
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN
:
Gas electrovalve is off for 5 seconds (with central flame control unit on).
RESET METHOD
:
Reset occurs automatically if the gas electrovalve switches on again within 10 minutes (with central flame
control unit on).
E 629
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN
: Code
U
629 is active for more than 10 minutes (with central flame control unit on).
RESET METHOD
:
Carry out appropriate checks. Reset may be performed via S61 board, menu 2, parameter 1 (or via
DDC). If the code persists, contact ROBUR TAC.
U
631
WATER TEMPERATURE TOO HIGH
CODE GENERATED BY
:
The warning appears when the water temperature is higher than the operational limits (heating).
RESET METHOD
:
Reset occurs automatically with 3.6°F hysteresis
U
632
WATER TEMPERATURE TOO LOW
CODE GENERATED BY
:
The warning appears when the water temperature is lower than the operational limits (cooling).
RESET METHOD
:
Reset occurs automatically with 3.6°F hysteresis
Summary of Contents for GAHP Line AR Series
Page 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Page 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Page 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Page 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Page 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...