GAHP-AR – Installation, start-up, use and maintenance manual
12
Edition:
2014-08
Table 7
-
Pressure drop – heating mode
GAHP-AR
∆
P evaporator
Outlet water temperature
Chilled water flow
37.4°F 44.6°F 50.0°F
GPM
∆
P
ft of Head
∆
P
ft of Head
∆
P
ft of Head
11.01 8.55 8.11 7.84
11.45 9.15 8.67 8.39
11.89 9.77 9.25 8.96
12.33 10.40 9.85 9.54
12.77 11.05 10.46 10.15
13.21 11.71 11.08 10.76
13.65 12.38 11.72 11.40
14.09 13.07 12.38 12.04
Table 8
-
Pressure drop – chilling mode
GAHP-AR
∆
P condenser/absorber
Outlet water temperature
Hot water flow
122.0°F 104.0°F 86.0°F
GPM
∆
P
ft of Head
∆
P
ft of Head
∆
P
ft of Head
6.60 3.05 3.08 3.15
7.04 3.30 3.32 3.35
7.48 3.58 3.62 3.65
7.93 3.89 3.98 4.05
8.37 4.25 4.35 4.42
8.81 4.64 4.76 4.86
9.25 5.05 5.19 5.28
9.69 5.50 5.66 5.77
10.13 5.96 6.18 6.29
10.57 6.45 6.66 6.83
11.01 6.95 7.16 7.39
11.45 7.47 7.68 7.97
11.89 7.99 8.21 8.57
12.33 8.52 8.76 9.18
12.77 9.06 9.32 9.80
13.21 9.59 9.90 10.43
13.65 10.12 10.50 11.07
14.09 10.64 11.11 11.72
14.53 11.36 11.81 12.60
14.97 11.98 12.48 13.35
15.41 12.63 13.17 14.12
15.85 13.29 13.87 14.91
16.29 13.97 14.60 15.72
16.73 14.67 15.35 16.55
17.17 15.39 16.11 17.40
17.61 16.13 16.90 18.27
18.05 16.88 17.70 19.16
18.49 17.65 18.53 20.07
18.93 18.44 19.37 21.00
19.37 19.25 20.23 21.94
19.81 20.08 21.11 22.91
20.25 20.92 22.01 23.90
20.69 21.78 22.93 24.90
21.13 22.66 23.87 25.93
21.57 23.56 24.82 26.97
22.01 24.48 25.80 28.03
Summary of Contents for GAHP Line AR Series
Page 6: ...GAHP AR Installation start up use and maintenance manual 2 Edition 2014 08 ...
Page 30: ...GAHP AR Installation start up use and maintenance manual 26 Edition 2014 08 ...
Page 52: ...GAHP AR Installation start up use and maintenance manual 48 Edition 2014 08 ...
Page 61: ...Electrical installer section Ed 2014 08 57 Figure 22 Internal electrical wiring diagram ...
Page 82: ...GAHP AR Installation start up use and maintenance manual 78 Edition 2014 08 ...