![Roberts Gorden Vantage CTH2V-100 Installation, Operation & Service Manual Download Page 49](http://html.mh-extra.com/html/roberts-gorden/vantage-cth2v-100/vantage-cth2v-100_installation-operation-and-service-manual_1469690049.webp)
SECTION 9: G
AS
P
IPING
43
FIGURE 24: Gas Connection with Flexible Gas Hose
Shut-Off Valve (included
with gas hose) must be
parallel to burner gas
inlet. The 3" (8 cm)
displacement shown is
for the cold condition.
This displacement may
reduce when the
system is fired.
CORRECT POSITIONS
Horizontal
45°
End View
Vertical
(as shown left)
Alternate
positions
okay
Flexible Gas Hose
36" (91 cm) length
3" (8 cm)
max. displacement
Side View
Heater Movement
12"
(30 cm)
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench
when attaching gas hose.
Failure to follow these instructions can result
in product damage.
Description
Part Number
1/2" Flexible Stainless Steel Gas Hose (US Models)
91412200
3/4" Flexible Stainless Steel Gas Hose (US Models)
91412203
1/2" R
u
bber Type 1 Gas Hose (Canadian Models)
91412206
3/4" R
u
bber Type 1 Gas Hose (Canadian Models)
91412207
Description
Part Number
High Press
u
re Reg
u
lator - 2 psi
90207600
High Press
u
re Reg
u
lator - 5 psi
90207601
Summary of Contents for Vantage CTH2V-100
Page 2: ......
Page 4: ......
Page 6: ......
Page 58: ...CTH2V SERIES INSTALLATION OPERATION AND SERVICE MANUAL 52 ...
Page 59: ...SECTION12 TROUBLESHOOTING 53 12 2 Manifold Gas Pressure Setting ...
Page 64: ......
Page 65: ...2017 ...
Page 66: ......
Page 67: ......
Page 68: ......