9.
Specifications
General Specifications
Power Voltage
Standard Model
24~48VDC
-A Model
125VDC
-B Model
12VDC
Power Consumption
6 Watts (Maximum)
Wire Connectors
Screw down terminal block, 16~26AWG
Outputs 1~8
Normally Open or Normally Closed Relays
System Alarm Output
Normally Open/Closed Relay
Relay Maximum Rating
115VAC
1.08A
125VA
12VDC
3.00A
36 Watts
24VDC
2.50A
60 Watts
48VDC
1.25A
60 Watts
130VDC
0.46A
60 Watts
220VDC
0.27A
60 Watts
System Link Response Time*
One-To-One (TCP)
Typical 8ms, Maximum 45ms
One-To-Many (UDP)
< 15ms
Many-To-One (TCP)
< 250ms
* Specifications listed are based on direct connections. Network overhead
should be considered when calculating overall system response times.
Data Interface
Ethernet (RJ-45)
Data Rate
10/100Mbps IEEE 802.3 Compliant
Surge Protection
Varistor (MOVs) and automatic resettable fuse (PTC Thermistor)
DC Input Isolation
1.5kV
Construction
Steel and aluminum alloy, powder coated
Physical Dimensions
H 5.0” x W 2.0” x D 3.9” (127mm x 51mm x 100mm)
Not including connectors or DIN rail bracket
Mounting Style
Standard DIN rail (T-35) or wall mount (with included ears)
Operating Temperature
-40˚F to +158˚F (-40˚C to +70˚C)
Humidity
95%
MTBF
175,000 Hrs (Circuit Board Level)
Warranty
Limited Lifetime
Application Examples