Settings
Description
Many to One
(UDP)
When selected the Output device will use Multicast UDP to receive the input
sensor updates.
Multicast
Group IP
Enter the address of the multicast group you wish to link this input
unit to.
The address: 228.1.1.2 port: 6402 is the default multicast address
& port for both the Input and Output devices.
Caution
– Only 1 input device should be joined to a multicast group.
The address entered must be within the IANA multicast address range.
Port
Enter which port number you wish to use for Multicast UDP
messages.
Notes:
(1) Choose this option for linking multiple output units to one input device.
(2) IGMP v2 is supported by Smart Series Input/Output devices to allow multicast
routing if necessary.
Email Alert and
Active Alarm Relay
is on disconnect
When selected email notifications and the alarm relay will activate on system link
connection / disconnection.
Retain Relay State
when System Link
is Broken
When the Relay Output device loses its link to the input device and the relays will
remain in their current state.
Device Configuration