3.6 Control Series Setting:
This Setting is for selecting capacitor
bank values in control series mode
The Screen displays "CtL" followed by
previously set Control Series Value.
Pressing the will enter to edit value of
control Series.
The range of control series setting is "1 to 9"
and "u". selecting value from 1 to 9 select
control series which represents ratio of capacitor banks with respect to first
bank. selecting "u" select user defined capacitor bank values which
represents actual kVAR value ( not ratio )
select value using key and for setting the value press the Key.
The Control Series are as given below:
1. Control Series 1: {1,1,1,1,1,1,1,1}
2. Control Series 2: {1,2,2,2,2,2,2,2} Selecting 1 will show as above.
3. Control Series 3: {1,2,3,3,3,3,3,3}
4. Control Series 4: {1,2,3,4,4,4,4,4}
5. Control Series 5: {1,2,4,4,4,4,4,4} Selecting u will show as above.
6. Control Series 6: {1,2,3,6,6,6,6,6}
7. Control Series 7: {1,2,4,4,4,4,4,4}
Note: If control series 1 to 9 is
8. Control Series 8: {1,2,4,8,8,8,8,8}
selected then device will
9. Control Series 9: {1,1,2,4,8,8,8,8}
accept only C01 value.
Default control series Number is 1.
if "u" is selected
and default C1 value is 25 kVAR.
then all capacitor bank values
Default capacitor bank value for ‘U’ is
need to be entered
25 kVAR for all capacitor banks