4. Installation
Mounting of PFC is featured with easy “Clip- in” mounting. Push the instrument in panel slot
(size 92 x92 mm), it will click fit into panel with the four integral retention clips on two sides
of instrument.
If required Additional support is provided with swivel screws (optional) as shown in figure.
Easy Clip
- in
mounting
Swivel screw
As the front of the enclosure conforms to
IP 50. additional protection to the panel may
be obtained by the use of an optional panel
The PFC should be mounted in a
reasonably stable ambient temperature and
where the operating temperature is within
the specification . Vibration should be
gasket. The terminals at the rear of the
product should be protected from liquids.
kept to a minimum and the product should
not be mounted where it will be subjected
to excessive direct sunlight.
Caution
1. In the interest of safety and functionality this product must be installed by a qualified
engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of
this unit. Ensure that all supplies are de-energised before attempting any connection
disconnection.
3. These products do not have internal fuses therefore external fuses must be used to
ensure safety under fault conditions.
15