Switching ON and OFF 10 secs
Discharge Time 60 secs
Control Modes Self Optimized Intelligent Control Mode
Measurement:
Voltage Range 80....300 Vac , 240 V Nominal
Fundamental Frequency 50 Hz
Input voltage burden < 0.15 VA Approx.
Current (CT) X/1,X/5 onsite programmable
Minimum measuring current 10 mA
Maximum Current 6A (sinusoidal)
Input Current burden < 0.2 VA Approx.
Power Factor Accuracy ± 2º
Switching Outputs:
Number of Outputs 4 or 6 steps (without add-on module)
8 steps with add-on module
Switching Voltage Power Max. 250 Vac / 1000W
Alarm Indication:
Under Voltage Trip Value 85% of VLn
Trip Delay 5 Sec
Hysteresis 3%
Bank Tripping Yes
Over Voltage Trip Value 110% of VLn
Trip Delay 5 Sec
Hysteresis 2%
Bank Tripping Yes
Under Current Trip Value 1% of CT Primary
Trip Delay 5 Sec
Hysteresis 2%
Bank Tripping Yes