Rinnai Tankless Water Heater Installation and Operation Manual
39
1. Direct Vent
(Twin Pipe)
Twin Pipe Overview
Combustion air and exhaust vent directly through separate penetrations.
Twin Pipe Termination Clearances
Exhaust
12 in. (0.30 m)
minimum above
combustion air
opening
12 in. (0.30 m)
minimum
12 in. (0.30 m)
minimum
Combustion
Air
12 in. (0.30 m) above
grade or anticipated
snow level
Roof
Indicates area in which intake cannot be installed.
Intake
60 in.
min
12 in.
min
12 in.
min
12 in.
min
12 in.
min
12 in.
min
Intake
Exhaust
Figure 31
Figure 32: Twin Pipe Vertical
Termination of Multiple Water Heaters
Figure 33: Horizontal Vent and Combustion
Air Piping
Minimum clearance for
Ground/Grade/Snow Level