10
3
2
2
3
3
3
4
5
3
8
10 15
10
13
14
12
1
EAF
EAF
15
6
3
3
3
3
11
6 7
17 5
3
3
3
5
3
4
3
5
3
4
SYSTEM
OUTLET
SYSTEM
RETURN
LINE
DOMESTIC
WATER
UTILITIES
DISCHARGES
DISCHARGES
1
Boiler
2 System Manifolds
3 Shut-off valves
4 System pumps
5 Non-return valves
6 Automatic vent valve
7 Boiler safety valve
8 Boiler discharge tap
9 Storage heater safety valve
10 Charging the system
11 System expansion tank
12 Storage heater
13 Storage heater discharge tap
14 Domestic hot water expansion
tank
15 Softener filter
16 Pressure reducer
17 Condensation pump
1.10
Schematic diagram - system for heating and domestic hot water production
1.11
Instructions for the connection of the fuel tank
The dimensions of the fuel tank support structure should be ad-
equate for the dimensions of the tank and the weight of the
tank when full. If the fuel tank is located on the outside, this and
the coupling pipe should be thermally insulated.
1
Fuel tank
2 Air vent
3 Filling pipe
4 Drain valve pipe
5 Drain valve
6 Level indicator
7 Heater
8 Fuel supply pipe
9 Cut-off valve
10 Heater filter
H
9 10
8
7
1
2
4
5
6
3
The tank should be placed higher than the burner, with a differ-
ence of level H between the output of the fuel tank (9) and the
burner input (10) greater than 4 m. When the boiler is not being
used, empty the fuel tank to prevent corrosion.