25
CHAPTER
7
Maintenance
7.3
Problems and remedies
If the burner does not work properly, first you must:
1
check that the electric connections have been correctly performed;
2
make sure that the fuel is flowing;
3
check that all the adjustment parameters (e.g. boiler water temperature or boiler steam pressure) are correctly set.
OIL WORKING
Fault
Possible cause
Recommended remedy
The burner does not start
• No electrical power supply . . . . . . . . . . . . . . . . . . . .Close all switches - Check connec-
tions
• A limiter or safety control device is open. . . . . . . . . .Adjust or replace
• Control box lock-out . . . . . . . . . . . . . . . . . . . . . . . . .Reset control box
• Control box fuses blown . . . . . . . . . . . . . . . . . . . . . .Replace
• Erroneous electrical connections . . . . . . . . . . . . . . .Check connections
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
• Air pressure switch in operating position . . . . . . . . .Adjust or replace
• Contact 2 of the servomotor, terminals 11-8 . . . . . . .Adjust cam 2 or replace the
of the control box do not operate (SQM 10) . . . . . . .servomotor (SQM 10)
• Contact 2 of the servomotor, terminals 11-8 . . . . . . .Adjust cam 2 or replace the
of the control box do not operate (SQM 40) . . . . . . .servomotor (SQM 40)
The burner does not start and a
function lock out occurs
• Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . .Replace control box
The burner starts but stops at
maximum air damper setting
• Contacts 1 or 4 of the servomotor, or terminals 9-8 .Adjust cams 1 or 4 or replace the
of the control box do not operate (SQM 10) . . . . . . .servomotor (SQM 10)
• Contacts 4 or 6 of the servomotor, or terminals 9-8 .Adjust cams 4 or 6 or replace the
of the control box do not operate (SQM 40) . . . . . . .servomotor (SQM 40)
The burner ignites but then
blocks
Air pressure switch inoperative due to insufficient air pressure:
• Air pressure switch adjusted badly . . . . . . . . . . . . . .Adjust or replace
• Pressure switch pressure point pipe blocked . . . . . .Clean
is blocked
• Head wrong adjusted . . . . . . . . . . . . . . . . . . . . . . . .Adjust
The burner starts and then locks
out
• Fault in flame detection circuit . . . . . . . . . . . . . . . . .Replace control box
The burner stays in the pre-
purge stage
• Contacts 3 or 5 of the servomotor, or terminals . . . .Adjust cams 3 or 5 or replace
10-8, of the control box do not operate . . . . . . . . . . .the servomotor (SQM 10)
• Contacts 3 or 5 of the servomotor, or terminals . . . .Adjust cams 3 or 5 or replace
10-8, of the control box do not operate . . . . . . . . . . .the servomotor (SQM 40)
Summary of Contents for DB 4 LSM C13
Page 2: ......
Page 61: ...1...
Page 69: ...9 3 3 1 1 2 3 M12 X 25 1 2 1 2 3 3 D12015 10 7 3 4 1 1 6 5 6 2 4 3 3 20110636...
Page 71: ...11 3 3 3 12 A A 8 10mm 4 4 5mm 12 D8665...
Page 72: ...12 4 4 1 1 2 3 3 3 4 1 6 13 1 3 4 5 D8416 2 6...
Page 73: ...13 4 4 2 D7543 C GF HPG LPG MM PA PGM PGm RG SRV VE VPS VR VS 0 5 4 bar 500 mbar 14...
Page 75: ...15 5 5 2 SQM 10 1 4 2 3 5 6 7 1 2 0 20 3 20 4 5 20 130 1 4 17 D1500...
Page 78: ...18 5 5 5 19 20 21 D2213 D2215 19 20 21 D2214...
Page 79: ...19 5 5 6 EN 267 20 A B D3509 22 2...
Page 83: ...23 7 7 1 UV 70 A 187 V 100 A c c 100 F 1V c c 7 2 1 2 3 4 5 1 2 3 4 5 6 D1143 31...
Page 86: ...26 7 VR VR VS VR...
Page 87: ...27 8 SQM 10 MB PA PGM PO SM TA TB UV UV VF VR VRS VS 3 5 6 7 6 3 2 8 5...
Page 89: ......
Page 90: ......
Page 91: ......