49
INStAllAtION
Par.
Jbus
Mnemonic
Description
field
Default
Unit
Control panel
CCN
table
519
NIGHT_MODE_
STOP
Night mode end time
0:00°23:59
00:00
hh:mm
RW
GEN_CONF
520
SPARE_SENSOR_
TYPE
Replacement sensor type
0°5
0 = No
1 = 10 KOhms Thermistor
2 = 5 KOhms Thermistor
3 = 3 KOhms Thermistor
4 = Low pressure transducer
5 = High pressure transducer
0
-
RW
GEN_CONF
521
17D6H
UI_TYPE
Type of user interface
0°3
0 = No
1 = Clean contacts
2 = WUI remote control (Air Temp)
3 = command on board WUI (Water Temp)
0
-
RW
RW/No
Force
UI_CONF
522
UI_ACCESS
Access to parameters from
the UI
0°3
0 = Not allowed
1 = User parameters only
2 = User and service parameters
3 = All parameters
3
-
RW
UI_CONF
523
UI_COMM_
TIMEOUT
Interface communication
timeout
0°240
60
s
RW
UI_CONF
524
UI_bACKLIGHT_
TIMEOUT
backlight timeout
0°7
0 = backlight always off
1 = 15 seconds
2 = 30 seconds
3 = 1 minute
4 = 2 minutes
5 = 5 minutes
6 = 30 minutes
7 = Always on
2
-
RW
UI_CONF
525
UI_bUZZER_
ENAbLE
buzzer at the push of a
button
0/1
[No/Yes]
No
-
RW
UI_CONF
526
UI_TIME_
bROADCAST
Time transmission interface
0/1
[No/Yes]
Yes
-
RW
UI_CONF
527
SERVICE_
PASSWORD
Service password
0°9999
120
-
RW
UI_CONF
528
USER_PASSWORD User password
0°9999
0
-
RW
UI_CONF
541
1934H
POWER_LIMIT
Power limitation value
50°100
75
%
RW
RW/No
Force
CMP_CONF
542
NIGHT_LIMIT
Night limitation value
50°100
75
%
RW
CMP_CONF
543
DHW_LIMIT
DHW limitation value
50°100
100
%
RW
CMP_CONF
560
FLUID_TYPE
Fluid type
1°2
1 = Water (minimum set point in cooling 5รC)
2 = Medium brine (minimum set point in cooling
0รC)
1
-
561
EXTERNAL_PUMP_
CTRL
External main pump
control
0/1
[No/Yes]
0 [No]
-
RW
PMP_CONF
562
FLOW_CHEK_
PUMP_OFF
Flow controlled if pump off
0/1
[No/Yes]
1 [Yes]
-
RW
PMP_CONF
563
PUMP_ANTI_
STICKING
Anti-adhesive function
0/1
[No/Yes]
1 [Yes]
-
RW
PMP_CONF
564
PUMP_SAMPLE_
TIME
Standby pump sampling
time
5°240
15
min
RW
PMP_CONF
565
MAIN_PUMP_
LOGIC
Main pump logic
1°3
1 = Always on
2 = Sampling (WUI local, On/Off vs IAT)
3 = In accordance with the indoor ambient
temperature (remote WUI / IAT sensor)
1
-
RW
PMP_CONF
566
VAR_SPEED_
PUMP_LOGIC
Variable speed pump logic
0/1
0 = Variable speed (according to the vsp_max
parameter)
1 = Speed in accordance with the Delta T
1
-
RW
PMP_CONF
567
0237H
MIN_SPEED_
PUMP
Minimum pump speed
19°100
19
%
RW
RW/No
Force
PMP_CONF
568
0238H
MAX_SPEED_
PUMP
Maximum pump speed
19°100
100
%
RW
RW/No
Force
PMP_CONF
569
WATER_DELTA_T_
SETPOI
Setpoint Delta T
2.0°20.0
5.0
1/10 K
RW
PMP_CONF
570
PUMP_KP
Proportional Delta T Gain
-10000°-0.001
-6000
-
RW
PMP_CONF
571
PUMP_TI
Integral time Delta T
10°120
20
s
RW
PMP_CONF
572
PUMP_TS
Delta T sampling time
10°120
10
s
RW
PMP_CONF