57
fUNCtIONS
COOlING ClIMAtIC CURVES
0
2
4
6
8
10
12
14
16
18
20
15
20
25
30
35
40
45
K1
K2
Setpoint dell'acqua (°
C)
OAT (°C)
—
If the OAT is valid (not transmitted by the inverter, value out
of range, etc.), the water setpoint is equal to the current
minimum water temperature.
—
If the OAT is above the maximum current OAT threshold,
the water setpoint is equal to the maximum current water
temperature.
The climatic curve corresponds to the water setpoint for the
Home mode. To define the other occupancy modes, it is nec-
essary to configure the Night cooling offset [P408] and the Away
cooling offset[P409]:
COOlING ClIMAtIC CURVES RElAtED tO WORKING MODE HOME
0
5
10
15
20
25
10
15
20
25
30
35
40
45
50
Home
Sleep
Away
P409
P408
WSP (°
C)
OAT (°C)
RISCAlDAMENtO:
If the climatic heating curve[P581] รร configurata
da "0" a "12", the water set point will be calculated on the basis
of the selected heating climatic curve.
Twelve predefined heating climatic curves are available:
Climatic curve
OAt min.
OAt max.
temp. water min.
temp. water max.
K1
-7°C
20°C
20°C
38°C
K2
-5°C
20°C
20°C
33°C
K3
-9°C
20°C
20°C
45°C
K4
-8°C
20°C
40°C
50°C
K5
-5°C
20°C
40°C
55°C
K6
0°C
20°C
40°C
60°C
K7
-20°C
20°C
22°C
42°C
K8
-20°C
20°C
23°C
55°C
K9
-12,7°C
20°C
24°C
60°C
K10
-5,9°C
20°C
25°C
60°C
K11
-1,5°C
20°C
26°C
60°C