53
INStAllAtION
Par.
Jbus
Mnemonic
Description
field
Default
Unit
Control panel
CCN
table
755
MSL_COOL_KP
Proportional cooling M /
S Gain
-10000°0.001
-6000
-
RW
MSL_CONF
756
MSL_COOL_TI
Integral time cooling M / S
10°120
30
s
RW
MSL_CONF
757
MSL_COOL_TS
Cooling sampling time M / S
10°120
30
s
RW
MSL_CONF
758
MSL_PUMP_TYPE Pump type Master / slave
0°3
0 = No pump control
1 = Common pump
2 = Internal pump: operation in accordance with
the master and slave logic(Par.229)
3 = Internal plunger: stops when the unit is not
on call
2
-
RW
MSL_CONF
761
02F9H JbUS_SELECTION Enable Jbus control
0°3
0 = Jbus/Modbus disabled
1 = Jbus enabled
2 = Modbus enabled
3 = Jbus specific for user interface
3
-
RW
RW/No
Force
JbUSCONF
762
0086H
JbUS_ADDRESS Slave address Jbus
1°255
11
-
RW
RW/No
Force
JbUSCONF
763
0085H JbUS_bAUD_RATE Jbus communication speed
0°2
0 = 9600 baud
1 = 19200 baud
2 = 38400 baud
0
RW/No
Force
JbUSCONF
764
0087H
JbUS_FRAME_
TYPE
Jbus structure type
0°5
0 = No parity, 1 stop bit
1 = Odd parity, 1 stop bit
2 = Even parity, 1 stop bit
3 = No parity, 2 stop bits
4 = Odd parity, 2 stop bits
5 = Even parity, 2 stop bits
0
-
RW
RW/No
Force
JbUSCONF
765
JbUS_
ACTIVATION_CODE
0
JbUSCONF
766
0600H
JbUS_COMM_
TIMEOUT
0°600
600
RW/No
Force
JbUSCONF
767
MODbUS_
DISPLAY_OFFSE
0°61440
16384
JbUSCONF
768
MODbUS_
SETPOINT_OFFS
0°61440
32768
JbUSCONF
769
MODbUS_
CONFIG_OFFSET
0°61440
28672
JbUSCONF
770
MODbUS_
SERVICE_OFFSE
0°61440
36864
JbUSCONF