52
INStAllAtION
Par.
Jbus
Mnemonic
Description
field
Default
Unit
Control panel
CCN
table
710
DHW_VSP_SPEED Maximum pump speed in
DHW mode
19°100
100
%
RW
DHW_CONF
711
DHW_SCHEDULE_
DAYS
DHW program days
0°11111110
bitmap:
b7 : Monday
b6 : Tuesday
b5 : Wednesday
b4 : Thursday
b3 : Friday
b2 : Saturday
b1 : Sunday
b0 : unused
11111110
-
RW
DHW_CONF
712
DHW_START_TIME DHW start time
00:00°23:59
21:00
hh: mm
RW
DHW_CONF
713
DHW_STOP_TIME DHW stop time
00:00°23:59
06:00
hh: mm
RW
DHW_CONF
714
LEG_SCHEDULE_
DAYS
Anti-legionella DHW start
0°11111110
bitmap:
b7 : Monday
b6 : Tuesday
b5 : Wednesday
b4 : Thursday
b3 : Friday
b2 : Saturday
b1 : Sunday
b0 : unused
0
-
RW
DHW_CONF
715
LEG_STRT_TIME Anti-legionella DHW start
time
00:00°23:59
02:00
hh: mm
RW
DHW_CONF
716
SUM_MODE_OAT Summer mode OAT
threshold
15.0°30.0
20.0
1/10°C
RW
DHW_CONF
717
SUM_MODE_ON Summer mode ignition
delay
0°12
0
h
RW
DHW_CONF
718
SUM_MODE_OFF Summer mode shutdown
delay
0°12
0
h
RW
DHW_CONF
719
DHW_TT_
SENSOR_TYPE
Type of DHW tank sensor
0°3
0 = DHW Thermostat (thermal switch)
1 = DHW Sensor (thermistor 10 Kรร)
2 = DHW Sensor (thermistor 5 Kรร)
3 = DHW Sensor (thermistor 3 Kรร)
0
-
RW
DHW_CONF
720
DHW_TT_bIAS
bias DHW tank sensor
-5.0°5.0
0.0
1/10 K
RW
DHW_CONF
721
DHW_DT_TO_
START
Delta T AC tankS
2.0°10.0
5.0
1/10 K
RW
DHW_CONF
722
DHW_DT_TO_
STOP
Delta T EWT (DHW
shutdown)
0.0°5.0
1.0
1/10 K
RW
DHW_CONF
741
MSL_CODE_
ACTIVATION
Activation code master/
slave
0
MSL_CONF
742
MSL_SELECT
Master / slave enabling
0°2
0 = Disabilitato
1 = Master
2 = Slave
0
-
RW
MSL_CONF
743
SLAVE1_ADDR
Slave address n.1
0°239
0
-
RW
MSL_CONF
744
SLAVE2_ADDR
Slave address n.2
0°239
0
-
RW
MSL_CONF
745
SLAVE3_ADDR
Slave address n.3
0°239
0
-
RW
MSL_CONF
746
MSL_CAPACITY_
START
Power to start the next
unit at
30°75
75
MSL_CONF
747
MSL_CAPACITY_
STOP
Power to stop the next
unit at
1°25
25
MSL_CONF
750
CHWSTEMP_TYPE Tipo CHWSTEMP
0°3
0 = No CHWSTEMP sensor
1 = 10 KOhms Thermistor
2 = 5 KOhms Thermistor
3 = 3 KOhms Thermistor
2
MSL_CONF
751
CASCADE_TYPE Cascade tipe
0°2
0 = Start master and follow slaves. Stop from the
last slave to the master.
1 = Start and stop according to the operating
hours (leveling)
2 = All units start and stop simultaneously.
1
-
RW
MSL_CONF
752
MSL_HEAT_KP
Proportional heating M /
S Gain
0.001°10000
6000
-
RW
MSL_CONF
753
MSL_HEAT_TI
Tempo integrale
riscaldamento M/S
10°120
30
s
RW
MSL_CONF
754
MSL_HEAT_TS
Heating sampling time
M / S
10°120
30
s
RW
MSL_CONF