INStAllAtION
Par.
Jbus
Mnemonic
Description
field
Default
Unit
Control panel
CCN
table
573
ADD_PUMP_
LOGIC
Additional pump logic
0°4
0 = No additional pump
1 = Always on
2 = In accordance with the ambient temperature
(remote WUI)
3 = Always on, off when DHW mode is activated
4 = In accordance with room temperature (remote
WUI), but off when in DHW mode
0
-
RW
PMP_CONF
581
0870H
HEAT_CURV
Heating climatic curve
selection
-1 = No curve, fixed setpoint
0 = Custom curvePar.582/Par.585
1 = Heating curve #1
2 = Heating curve #2
3 = Heating curve #3
4 = Heating curve #4
รรร
12 = Heating curve #12
-1
-
RW
RW/No
Force
CLIMCURV
582
0876H CUST_HEAT_MIN_
OAT
Minimum OAT heating
-30.0°10.0
-7.0
1/10°C
RW
RW/No
Force
CLIMCURV
583
0877H CUST_HEAT_MAX_
OAT
Maximum OAT heating
10.0°30.0
20.0
1/10°C
RW
RW/No
Force
CLIMCURV
584
1902H CUST_MIN_TEMP_
HEAT
Minimum heating water
setpoint
20.0°40.0
20.0
1/10°C
RW
RW/No
Force
CLIMCURV
585
1904H CUST_MAX_TEMP_
HEAT
Maximum heating water
setpoint
30.0°60.0
38.0
1/10°C
RW
RW/No
Force
CLIMCURV
586
0875H
COOL_CURV
Cooling climatic curve
selection
-1°2
-1 = No curve, fixed setpoint
0 =Custom curve Par.587/Par.590
1 = Cooling curve #1
2 = Cooling curve #2
-1
-
RW
RW/No
Force
CLIMCURV
587
087bH CUST_COOL_MIN_
OAT
Minimum cooling OAT
0.0°30.0
20.0
1/10°C
RW
RW/No
Force
CLIMCURV
588
087AH CUST_COOL_MAX_
OAT
Maximum cooling OAT
24.0°46.0
35.0
1/10°C
RW
RW/No
Force
CLIMCURV
589
1903H CUST_MIN_TEMP_
COOL
Minimum cooling water
setpoint
5.0°20.0
10.0
1/10°C
RW
RW/No
Force
CLIMCURV
590
1905H CUST_MAX_TEMP_
COOL
Maximum cooling water
setpoint
5.0°20.0
18.0
1/10°C
RW
RW/No
Force
CLIMCURV
595
DRYING_START_
SETPOIN
Drying start setpoint
20.0°40.0
20.0
1/10°C
RW
DRYING
596
DRYING_WARM_
UP_DAYS
Heating drying days
0°99
3
-
RW
DRYING
597
DRYING_RAMP_
UP_DAYS
Days ramp upward drying
0°99
4
-
RW
DRYING
598
DRYING_HOLD_
UP_DAYS
Drying ramp maintenance
days
0°99
4
-
RW
DRYING
599
DRYING_HOURS Drying operation time
0.0
RW
DRYING
601
186AH
bCK_TYPE
Type of emergency addition
0°10
0 = No backup
1 = booster con 1 stage electrical heater
2 = booster con 2 stage electrical heater
3 = booster con 3 stage electrical heater with 2
output
4 = booster con 3 stage electrical heater with 3
output
5 = backup DHW
6 = booster con 1 stage electrical backup
DHW
7 = booster con 2 stage electrical backup
DHW
8 = booster con 3 stage electrical heater with 2
backup DHW
9 = backup with boiler
10 = backup with backup DHW
0
-
RW
RW/No
Force
bCK_CONF
602
186DH
bCK_WARMUP_
TIME
Heating time of the
additional heater
0°120
30
min
RW
RW/No
Force
bCK_CONF
603
1937H bCK_DELTA_TEMP Auxiliary delta temperature
1.0°20.0
5.0
1/10°C
RW
RW/No
Force
bCK_CONF
604
186CH
bCK_OAT
Additional heater OAT
threshold
-20.0°15.0
-7.0
1/10°C
RW
RW/No
Force
bCK_CONF
605
EHS_PROP_GAIN Proportional EHS Earnings
0.001°10000
2000
-
RW
bCK_CONF
606
EHS_INTEG_TIME Integral time EHS
10°60
20
s
RW
bCK_CONF
607
EHS_SAMP_TIME EHS sampling time
10°120
30
s
RW
bCK_CONF
611
DEFROST_TYPE Free defros enabled
0/1
1
bCK_CONF