INStAllAtION
Alarm
Inverter
Alarm [P350]
- [P354] or
[P360] -
[P364]
Description
Unit status
Reset type
Verifications
Automatic
feeding cycle
Comment
227
74
Discharge temperature too high
Stop cpr
X
This error becomes permanent after 4
attempts to complete the operation.
1. Check the refrigeration cycle (gas
leak)
2. Electronic expansion valve
problems
3. Check the discharge temperature
sensor (TD).
229
75
Phase missing in the power cable
Stop cpr
X
This error becomes permanent
after 8 attempts to complete the
operation.
1.Check the supply voltage.
231
76
Inverter heatsink temperature too high
Stop cpr
X
This error becomes permanent after 4
attempts to complete the operation.
1. Check the explosion path of the
heatsink.
-
78
Other Inverter errors
Continue
X
-
79
Unknown errors Inverter
Continue
X
-
80
RTC fault on NHC board
Continue
X
-
81
EEPROM damaged on board NHC
Continue
X
127
82
EEPROM inverter not readable or
EEPROM number out of range
Stop
X
Simple delay in communication.
-
90
Invalid configuration
Stop
X
-
100
Invalid configuration
Stop
X
Automatic when[P055] is reset.
-
200
External alarm
Continue
X
When the contact is closed