96
MANAGING ADDITIONAL ZONE
6.2
Setting parameters of the additional zone
Controls interface
2
1
3
4
5
6 7
9
8
10
1
255x80 point backlit display (106,4x39,0mm)
2
RESET key: restores normal operations after a safety shut-down
3
MENU key: switches on the main menu
4
ESC key: in menu navigation, it enables you to exit a menu item and go back to the previous
one
5 ÷ 9
Navigation keys
◄
,
▼
,
●
,
►
,
▲
10
Main switch (located on the lower part of the appliance)
6.3
Setting zone parameters (accessible only with installer password)
Menu
→
“Settings”
→
“Zone Config.”
This menu allows you to separately set the parameters of all the connected zones with the exception of the “Extra setpoint zone”
which is the same for all zones.
To select the zone for controlling/changing the parameters, proceed as follows:
− press the
►
key so that the number to the right of “zone” is highlighted;
− once the number is highlighted use the
▲
and
▼
keys to change the number of the zone;
− once the zone is selected, confirm with the
●
key.
The zone parameters are the following:
Description
Standard value that
is set
Range
Explanation
UM
Post-circ. Zone Pump
120
0-255
Establishes the time in seconds of the
post-circulation
Secs
Mix Valve Max Op/Cl Time
25
0-255
Fixes the time in second of the total
opening/closing of the mix valve (valid
for three point mix valve)
Secs
Mix Valve Max steps
700
0-65535
Fixes the number of steps for the total
opening of the mix valve (valid for step-
by-step mix valve)
PID zone mode
Symmetrical
Symmetrical/Asymmetrical
Fixes the PID control mode
PID P Zone
10
0-255
Proportional parameter for the valve
control
PID I Zone
150
0-255
integrativee parameter for the valve
control
PID D Zone
0
0-255
Derivative parameter for the valve control
Extra zone setpoint
10
0-30
Establishes the increase for the pri-
mary setpoint with respect to the zone
setpoint
°C
9
For more information regarding navigating the commands interface (thermal module display) see the paragraph "Electronic
control".