93
ZONE DEPENDING
5
ZONE DEPENDING
5.1
Zone control with Depending module
The thermal elements Depending on the
Steel Pro Power
are
prepared as standard to be configured as zones.
Thus, for example, a thermal module with 4 thermal elements
will be set up as standard for the management of 3 zones (one
for each Second thermal element) installed inside the thermal
module itself.
To enable the functioning of the element as a zone, the proce-
dure described below must be carried out.
Boiler
Parameters DEP n°
(205)
Dep. Zone Control
Boiler Settings
Settings
Home/Menu
screen
− Select "Enabled" and confirm
Access the following menu:
DEP n°
(97) Appliance
Configuration
Config.
dispositivo
Settings
Home/Menu
screen
− Choose 19 (pump versions) or 18 (valve versions)
− Select "CONFIRMED CONFIG"
− Select "YES"
− Wait for initialization and finalization.
The (temporary) error appears on the initial screen 164 and then
the error 208 that signals that the zone probe is not connected.
At this point the zone is ready to be connected as reported in the
paragraph "Typical water system schematics".
5.2
Setting zone parameters (accessible only with installer password)
Menu
→
"Settings"
→
"Config. area dep "
This menu allows you to separately set the parameters of all the connected zones with the exception of the “Extra setpoint zone”
which is the same for all zones.
To select the zone for controlling/changing the parameters, proceed as follows:
− press the
►
button so that the number to the right of the word "zona dep." is highlighted;
− once the number is highlighted use the
▲
and
▼
keys to change the number of the zone;
− once the zone is selected, confirm with the
●
key.
The zone parameters are the following:
Description
Standard value that
is set
Range
Explanation
UM
Mix Valve Max Op/Cl Time
25
0-255
Fixes the time in second of the to-
tal opening/closing of the mix valve
(valid for three point mix valve)
Secs
PID P Zone
10
0-255
Proportional parameter for the
valve control
PID I Zone
150
0-255
integrativee parameter for the
valve control
PID D Zone
0
0-255
Derivative parameter for the valve
control
Extra zone setpoint
10
0-30
Establishes the increase for the
primary setpoint with respect to
the zone setpoint
°C
The setting of the parameters of the climatic curve and the programming of the dependent zone is identical to that of the additional
external zone, as described in the paragraphs "Setting zone's climatic curve parameters (accessible only with installer password)"
and "Programming the zone".