105
SYSTEM MANAGER
MODBUS CONNECTION
Status parameters
Register
number
Access
Description Automatic
conversion
Value
range
L
S
100
X
State
See "State"
table
101
X
Status
See "Sta-
tus" table
102
X
Error code
See "Error"
tables
103
X
Alarm code
See "Warn-
ing" table
110
X
Heating
pump
Yes
0/100 or
0..100%
111
X
DHW pump Yes
0/100 or
0..100%
112
X
Module
pump
Yes
0/100 or
0..100%
Temperatures/Information
Register
number
Access
Description Automatic
conversion
Value
range
L
S
120
X
Delivery
temperature Yes
Depends
on °C/°F
units
121
X
Return tem-
perature
Yes
Depends
on °C/°F
units
122
X
DHW tem-
perature
Yes
Depends
on °C/°F
units
123
X
Flue gas
temperature Yes
Depends
on °C/°F
units
124
X
System
tempera-
tures (where
available)
Yes
Depends
on °C/°F
units
125
X
Outdoor
tempera-
ture (where
available)
Yes
Depends
on °C/°F
units
140
X
Power
Yes
0..100%
141
X
Minimum
output
Yes
0..100%
142
X
Ionisation
current
Yes
0..x μA
Dependent information
Register
number
Access
Description Automatic
conversion
Value
range
L
S
Dependent 01
300
X
State
See "State"
table
302
X
Error code
See "Error"
tables
303
X
Power
Yes
0..100%
Dependent 02
306
X
State
See "State"
table
308
X
Error code
See "Error"
tables
309
X
Power
Yes
0..100%
Dependent 03
312
X
State
See "State"
table
314
X
Error code
See "Error"
tables
315
X
Power
Yes
0..100%
Dependent 04
318
X
State
See "State"
table
320
X
Error code
See "Error"
tables
321
X
Power
Yes
0..100%
Dependent 05
324
X
State
See "State"
table
326
X
Error code
See "Error"
tables
327
X
Power
Yes
0..100%
Dependent 06
330
X
State
See "State"
table
332
X
Error code
See "Error"
tables
333
X
Power
Yes
0..100%
Dependent 07
336
X
State
See "State"
table
338
X
Error code
See "Error"
tables
339
X
Power
Yes
0..100%
Dependent 08
342
X
State
See "State"
table
344
X
Error code
See "Error"
tables
345
X
Power
Yes
0..100%