COMMISSIONING AND MAINTENANCE
The parameters regulating such temperature are:
Par.
No. Description
3
Sets the desired flow temperature with heating mode.
Active for the heating mode Par. 1 = 0 o 3
23
Limits the minimum value that can be assigned to the
set-point in heating mode (does not apply to heating
mode 4).
24
Limits the maximum value that can be assigned to the
set-point in heating mode (does not apply to heating
mode 4).
Delivery Temp.
(°C)
Outdoor Temp. (°C)
Tset min (°C)
Tset max (°C)
Setpoint
Par. 24
Par. 23
Par. 03
Mode 1
(Climatic functioning with room/heat demand thermostat, vari-
able set point according to the outdoor temperature)
In this case the thermal module operates with a variable set-
point depending on outdoor temperature based on a climatic
curve defined by the following parameters:
Par.
No. Description
109 Defines the value of the set point calculated on climat-
ic mode (Par. 1 = 1).
19
Establishes the max. set-point at the minimum out-
door temperature for climatic regulation
20
Establishes the minimum outdoor temperature to
which the maximum set-point can be associated for
climatic regulation
21
Establishes the minimum set-point at the maximum
outdoor temperature for climatic regulation
22
Establishes the maximum minimum outdoor tempera-
ture to which the minimum set-point can be associat-
ed for climatic regulation
23
Limits the minimum value that can be assigned to the
set-point in heating mode (does not apply to heating
mode 4).
24
Limits the maximum value that can be assigned to the
set-point in heating mode (does not apply to heating
mode 4).
25
Defines the temperature at which climatic regulation is
switched off
Delivery Temp.
(°C)
Outdoor Temp. (°C)
Tset min (°C)
Tset max (°C)
Par. 109
Par. 24
Par. 23
Par. 20
Par. 22
Par. 25
Par. 19
Par. 21
The demand is activated when the room/heat demand thermo-
stat's contact is closed provided that outdoor temperature does
not exceed the value set by the parameter 25.
if the outdoor temperature is higher than the one set on param-
eter 25 , the burner is stopped even if there is a heat demand.
The climatic curve can also be adjusted in a simpler, more us-
er-friendly way.
Enter the "CH" menu. The following display will appear:
“
Central Heating (CH)
”
“
Outdoor reset
”
Press the
●
key to confirm and enter the climatic curve screen.
“
Outdoor reset
”
“
Setp. [°C]
”
194
32
5
95
“
Des. Supply T.
”
82.0
“
°C
”
“
Bas. Supply T.
”
40.0
“
°C
”
“
WW Shutdown
”
21.0
“
°C
”
“
Bas. Outd. T.
”
21.0
“
°C
”
“
T Outside [°C]
”
“
Des. Outd. T.
”
-4.0
“
°C
”
"Design Supply Temp." and "Design Outdoor Temp." will be dis-
played. To change their value, press the
●
key.
1
Use the
▲
/
▼
keys to modify Design Supply Temp and the
◄
/
►
keys to change Design Outdoor Temp.
2
Press
●
to save changes
3
Use the
◄
/
►
keys to select other values.
Repeat steps 1 from 3 to make other changes.
After setting the parameters, press the ESC key to exit the menu.
9
If the outdoor temperature sensor (accessory) is not detect-
ed (not installed or damaged) the system provides a warn-
ing: no. 202
The presence of the warning does not stop the thermal
module allowing a heat request to be carried out at the
maximum setpoint set on the climatic regulation.