22
23
OPEN SLOW SPEED
When the door is approaching open limit and decelerates down to slow speed before the
stop (Soft Stop), added force/speed may be required to complete opening. While this is
indcative of an improperly balanced door, this feature can be used to compensate. This
setting should only be changed from the NORMAL to the HIGH setting if door becomes
unbalanced over time and does not completely travel to Open limit. If it is a new installation,
changing the spring tension for proper balance is a required first step. Factory default is
‘NORMAL’.
CLOSE SLOW SPEED
When the door is approaching Close Limit and decelerates down to slow speed before
the stop (Soft Stop), added force/speed may be required to complete closing. While this
is indcative of an improperly balanced door, this feature can be used to compensate. This
setting should only be changed from the NORMAL to the HIGH setting if door becomes
unbalanced over time and does not completely travel to Close limit. If it is a new installation,
changing the spring tension for proper balance is a required first step. Factory default is
‘NORMAL’.
OPEN RAMPDOWN DISTANCE
This setting is used to change the point where the door begins to decelerate to slow speed
as it approaches the Open Limit. The user can choose between auto (which is configured by
the system) or the desired number of shaft rotations (between 0.5 turns and 3 turns in half
rotation increments).
The Factory setting for this feature is AUTO. This should not be changed unless
recommended by Dyna-Hoist Technical Support.
CLOSE RAMPDOWN
DISTANCE
This setting is used to change the point where the door begins to decelerate to slow speed
as it approaches the Close Limit. The user can choose between auto (which is configured by
the system) or the desired number of shaft rotations (between 0.5 turns and 3 turns in half
rotation increments).
The Factory setting for this feature is AUTO. This should not be changed unless
recommended by Dyna-Hoist Technical Support.
OPEN LIMIT OPTIONS (PUSH BUTTON)
This setting allows the user to choose between the SET LIMIT or the FULLY OPEN limit for
the "OPEN" button on the control panel or the "O" terminal (Push Button Station Inputs) on
the control circuit board.
OPEN LIMIT OPTIONS (REMOTE RADIO)
This setting allows the user to choose between the set limit or the fully open limit for the
"REMOTE RADIO" connections on the control circuit board.
OUTPUT RELAY OPTIONS
The Output Relay is used for signalling/interlocking with other devices such as a dock
leveller, security equipment, other doors, etc. There is one NO and one NC contact available
that can be energized at either the open or closed limit, as chosen by the user in this setting.
The Factory setting for this feature is ENERGIZED WHEN OPEN.
CALIBRATION