35
from the check.
If the motor does not work during this check, check the connections and its capacitor.
If the motor is working properly, check the safety devices.
TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having
positioned the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7,
DL8, DL9 and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL6
OFF
Stop button malfunction (if Stop is not connected, perform
the jump between COM A+ and STOP).
DL7 or DL8
OFF
Faulty photocells (In case the edge is not connected, carry
out jumper between COM A+ and PHOTO 1/PHOTO 2)
DL9 or DL10
OFF
Faulty safety edge (In case the edge is not connected, carry
out jumper between COM A+ and EDGE 1/EDGE 2)
LED DL13 (BLUE)
ON
Some functions are enabled via smartphone, so via
smartphone check the card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause
of the fault.
FAULT
SOLUTION
After having carried out the various connections and having supplied voltage, all the LEDS
are switched off.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause
of the fault.
Check the integrity of fuse F1.
In case of interrupted fuse use only of adequate value
F1 = T 5A Fuse for motor protection
The motor opens and closes, but it has no strength and moves slowly.
Check trimmers TORQUE and LOW-SPEED adjustment.
The gate opens but does not close after the time set.
Make sure that the TCA trimmer is activated with LED DL11 ON.
B.I.O. contact always on / green led on => check the status of the clock connected to B.I.O.
input.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
The gate does not open or close by activating the various START, RADIO, OPEN and CLOSE
buttons.
Faulty safety edge contact. Faulty photocells contact with
DIP 4
OFF. => Fix or replace the
faulty contact.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
By activating the START, OPEN or CLOSE button the gate does not move.
START, OPEN or CLOSE command always active.
Check and replace any buttons or micro-switches of the selector switch.
The slowing phase is not performed.
Ensure that
DIP 9
is in ON position (Slowdown enabled).
Perform the programming times procedure with
DIP 2
.
Check LOW SPEED trimmer adjustment.
G
B