(by starting the opening movement only after the obstacle is removed) and
closing (by starting the reverse movement only after the obstacle is removed).
DIP 4 ON =>
if an obstacle is placed in range of the photocells when the gate is closed
and the command to open is given, the gate opens (the photocells do not
work while opening). Photocells work only during closing (with reverse motion
restored after a second, even if they are still engaged).
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply
is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal A -, to
shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
MONITORING OF PHOTOCELLS (A+ TEST A-)
Connect the photocell transmitter to A+ TEST/A- and set
DIP 7
to ON.
The monitoring consists of a functional test of the photocell run before every movement.
The gate movement is therefore permitted only if the photocells have passed the functional
test.
CAUTION:
MONITORING OF THE PHOTOCELLS INPUTS (PHOTO 1/PHOTO 2) CAN BE
ACTIVATED WITH
DIP 7
ON OR DEACTIVATED WITH
DIP 7
OFF.
WARNING: If the AUTOTEST feature is enabled and only one photocell is connected,
a jumper must be made between the PHOT 1 and PHOT 2 terminals. If
the jumper is not made, the AUTOTEST fails and the gate will not move.
PHOTOCELL AUTOTEST ALARM (DIP 7 ON)
If the photocell fails the monitoring test, an alarm is displayed by the blinker lighting up
and gate movement is not allowed. Normal operation can be restored only by repairing the
photocell and pressing one of the controls.
EDGES (SAFETY STRIPS) (COM A+/EDGE 1, COM A+/EDGE 2)
If engaged when closing, EDGE 1 reverses the motion in opening. If edge remains engaged,
it doesn’t permit the closing.
If engaged during opening, EDGE 2 reverses the motion in closing. If edge remains engaged,
it doesn’t permit the opening.
If edges are not used, jump the terminals COM A+/EDGE1/EDGE2.
EDGE ALARM
Flasher and buzzer are activated with 2 tones every 5 seconds for one minute.
STOP BUTTON (COM A+/STOP)
The STOP button stops the gate during any operation.
If held when the gate is fully open (or partially when using the pedestrian control) automatic
closing is temporarily deactivated (if activated by the TCA trimmer and LED DL11 on). It is
therefore necessary to use a new command to make it close.
The automatic closing function is reactivated on the next cycle (if activated by the TCA
trimmer and LED DL11 ON).
FUNCTIONING IN HOLD-TO-RUN MODE WHEN THE SAFETY DEVICES ARE FAILING
If one of the safety edges fails or remains engaged for more than 5 seconds, or if one of the
photocells fails or remain engaded for more than 60 seconds, the OPEN, CLOSE, START and
PED. commands will work only in hold-to-run mode.
The signal that this mode has been activated is given by the blinking of the programming
led DL1.
The radio commands and the automatic closing will be excluded, since their use in this mode
is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands
functioning again so radio commands and the automatic closing will be enabled again.
Note 1:
during this functioning in hold-to-run mode, in case of damage to the safety strips
(or photocells) the photocells (or safety strips) still work by interrupting the operation
in progress.
Note 2:
the stop command is not to be considered a safety command that can be bypassed
in this mode. Therefore, when pressed or damaged, it will not allow any movement
of the gate.
The hold-to-run mode is only an emergency operation which must be activated for a
very short period and with the complete installation at sight so to have a secure and
safe control of the system. As soon as possible however, the failing safety devices
must be repaired and activated.
VISUAL AND SOUND ALARMS
BLINKER
Connect the flashing light to the blinker output, use flashing lights ACG7059 and bulbs of
40W maximum.
PRE-BLINKING
DIP 5
- OFF => motor and blinker start simultaneously.
DIP 5
- ON => blinker starts 3 seconds before the motor.
BUZZER
It has the task to signal the intervention of the security, the anomalies and the memorization
and cancellation of the radio codes.
SIGNAL - 24Vdc GATE OPEN WARNING LIGHT (COM A+/SIGNAL-)
Signals when the gate is open, partially open or not closed completely. It turns off only when
the gate is completely closed.
During opening, it flashes slowly.
When the gate is stationary or opened, it is permanently on.
During closing, it flashes quickly
N.B.: Max 3 W. If warning lights are in excess, the control panel processes will be
endangered with possible stop of all operations.
OPERATION AFTER BLACK-OUT
At the time of the blackout, gate status is saved in the memory.
When mains voltage is restored:
If the gate is located on the
opening or closing limit switch, operating the control will close
or open the gate with the saved data.
If the gate is in intermediate position
, operating the control will open the gate slowly until
it reaches the opening limit switch. After completing this first movement, the operator will
resume work at the set speed.
TECHNICAL SPECIFICATIONS
- Humidity
< 95% without condensation
- Power voltage
230V~ ±10% (120V/60Hz upon
request)
- Frequency
50/60Hz
- Maximum board absorption
30mA
- Interruptions in electricity supply
100ms
- Maximum load of open gate output
3 W (equal to 1 3W bulb or to 5 LEDs
connected in series through a resistor
of from 2.2 Kohm)
- Blinking unit maximum output load
40W with resistive load
- Current available for photocells and accessories 400mA 24Vdc
- Current available on radio connector
200mA 24Vdc
- ALL THE PUSH BUTTONS, INPUTS AND COMMANDS CONNECTED TO THE CONTROL
BOARD MUST BE CLEAN CONTACT.
TECHNICAL RADIO SPECIFICATIONS (Only L1-CRX)
- Reception frequency
433,92MHz
- Impedance
52
Ω
- Sensitivity
>2.24µV
- Excitation time
300ms
- De-excitation time
300ms
- Codes in store
N° 1000 total
- All the inputs must be used as clean contacts because the power supply is generated
internally (safe voltage) in the card and it is set in a way to guarantee the use of the double
insulation and reinforced in relation to parts with hazardous voltage.
- Any external circuits connected to the outputs of the control board, must be carried out to
make sure the double or reinforced insulation is used in relation to parts with hazardous
voltage.
- All the inputs are run by a programmed integrated circuit which carries out a self-check at
the beginning of each operation.
MAINTENANCE CHECK
N.B.: During this check the safety functions Edges, Photocells, Stop button and
Impact detection are NOT active.
1 - Set
DIP 1
to ON => LED DL1 starts to flash.
2 - Press and hold the PROG button (the command is hold-to-run, open-stop-close-stop-
open-etc ...) => The gate starts at high speed and then slow down until the limit switch
is reached.
3 - At the end, put
DIP 1
back to the OFF position. The DL1 LED turn off signaling the exit
24Vdc
Term.
A -
G
B