ENCLOSED DOCUMENTS
90
A2 TECHNICAL
DATA
TCCE - THCE
114
117
121
126
114 T
114 H 117 T 117 H
121 T
126 T
Nominal cooling capacity (*)
kW
14,1
16,6
21,2
25,4
14,1
14,1
16,6
16,6
21,2
25,4
E.E.R.
2,47
2,60
2,65
2,61
2,47
2,47
2,60
2,60
2,65
2,61
Nominal heating capacity (**)
kW
14,3
17,3
21,5
25,6
15,3
15,3 18,7 18,7
23,2
28,3
C.O.P.
2,51
2,73
2,78
2,77
3,16
3,16
3,39
3,39
3,34
3,37
Sound pressure (***)
dB(A)
54
55
56
57
54
54
55
55
56
57
Scroll compressor
No.
1
1
1
1
1
1
1
1
1
1
Fans 2x
kW
0,56
0,56
0,56
0,56
0,56
0,56
0,56
0,56
0,56
0,56
Fan E.S.P.
Pa
90
80
90
80
90
90
80
80
90
80
Water side exchanger nominal water flow (*)
l/h
2417
2871
3637
4365
2427
2427
2871
2871
3637
4365
Exchanger water contents
l
1,50
1,70
1,90
2,40
1,50
1,50
1,70
1,70
1,90
2,40
Nominal pressure drops, water side exchanger (*)
kPa
17
17
22
16
-
-
-
-
-
-
Pump external static pressure (*)
kPa
-
-
-
-
47
174 41 154
151
139
Storage tank water content
l
-
-
-
-
55
55
55
55
80
80
R407C refrigerant charge
●
kg
see serial number plate
see serial number plate
R407C refrigerant charge (THCE)
●
kg
see serial number plate
see serial number plate
Polyester oil charge
▲
kg
1,90
1,60
3,15
3,15
1,90
1,90
1,60
1,60
3,15
3,15
Polyester oil charge (THCE)
▲
kg
1,90
1,60
3,15
3,15
1,90
1,90
1,60
1,60
3,15
3,15
TCCE weight
kg
250
270
330
360
340
340
360
360
420
460
THCE weight
kg
270
280
350
370
350
350
370
370
440
440
Electrical data
114
117
121
126
114 T
114H 117 T 117 H
121 T
126 T
Total absorbed power (summer operation) (*)
kW
5,70
6,43
7,99
9,73
5,89
6,35
6,62
7,08
8,64
10,38
Total absorbed power (winter operation) (**)
kW
5,70
6,43
7,99
9,73
5,85
6,31
6,52
6,98
8,41
9,85
Electrical power supply
V-ph-Hz
400-3-50
400-3-50
Auxiliary power supply
V-ph-Hz
230-1-50
230-1-50
Nominal current (summer operation)
A
13,4
14,1
16,7
19,3
14,2
16,4 15,0 17,2
19,8
22,3
Nominal current (winter operation)
A
13,6
14,5
17,1
19,7
14,4
16,6
15,3
17,5
20,1
22,7
Max. current
A
15,0
16,6
19,3
22,3
15,9
18,1 17,5 19,7
22,3
25,3
Starting current
A
66
74
98
130
66
66
74
74
98
130
Water connections
114
117
121
126
114 T
114H 117 T 117 H
121 T
126 T
Water inlet/outlet
Ø
1 ½”G (male)
1 ½”G (male)
Condensation drain (THCE only)
Ø
30 mm
30 mm
Storage tank train (T versions only)
Ø
- ½”G
(Female)
(*) In the following conditions: condenser input air temperature 35°C; chilled water temperature 7°C; temperature differential at evaporator
5°C.
(**) In the following conditions: evaporator input air temperature 6°C W.B.; hot water temperature 45°C; temperature differential at evaporator
5°C.
(***)Sound pressure level in dB(A) measured at a distance of 5 m from the unit, with directionality factor of 2 and ducting on the fan outlet.
●
Check the serial number plate attached to the machine.
▲
Check the plate attached to the compressor.
N.B. The C.O.P. and EER calculation do not take the electric power absorbed by the circulating pump into account.