1. Set furnace in place and connect the
a. Openings in the side must be cut
out the full width of the knockouts
on the unit. If using side return air,
THE BOTTOM base plate must
be installed
airflow is 1800 CFM or more, both
sides or the bottom must be used
for return air.
b. If using bottom return air, place
furnace over return air plenum and
seal furnace bottom to return air
plenum.
2. If summer air conditioning is desired,
position the indoor coil on the top of
the unit. Insure that no air can
bypass this coil.
3. Connect the supply air plenum to the
1. Position the unit over the supply air
a. If installing on a combustible floor
and not using an evaporator
coil box,
combustible floor base.
See Figure 4.
b. If summer air conditioning is
desired, position the indoor coil on
the bottom of the unit. Insure that
no air can bypass this coil.
2. Connect the return air ducting to the
1. Position the unit on adequate
supports or by using support
brackets (see Figure 1) and connect
supply plenum.
2. If summer air conditioning is desired,
position the indoor coil on the supply
air side of the unit. Insure that no air
can bypass this coil.