supply pressure to the furnace should
be 10.5” w.c. for natural gas and 13”
w.c. for LP gas.
Natural gas supply pressure should
operate between 5" to 10.5
gas supply pressure should be 11
maintained with all other gas-fired
appliances in operation.
NOTE: Do not exceed a gas pressure
of 13” w.c.
Orifice size information is shown on the
table below:
For installation, see specific LP
kit installation instructions.
Order the correct LP conversion
1. Turn off all electrical power and the
2. Remove the burner door from the
3. Remove the igniter assembly –
4. Remove the two screws attaching
the NOx insert retainer brackets to
the center panel. Pull the retainer
rod.
5. Put the two screws back into the
6. Re-install the igniter and burner