100518834 – Rev. B
8.3.2
Low Outlet Pressure Alarm –
Occurs when the Outlet Pressure
(
OUTP
) drops below the alarm
set point for more than one (1)
minute. (Default setting is 6.5
PSI for W models, 0.30 PSI for WLP models)
See section 13.7 for troubleshooting information.
8.3.3
High Flow Rate Alarm –
Occurs when the Flow Rate
(
FLOW
) rises above the alarm
set point for more than one (1)
minute. (Default setting is 500
SCFD (14.2 SCMD))
8.3.4
High Humidity Alarm –
Occurs when the Humidity level
rises above the alarm set point
for more than one (1) minute.
(Default setting is 10.0%)
If this alarm is present for one
(1) minute or more, the air Dryer
will go into
SHUTDOWN
mode to prevent saturated air
from being delivered to the supply line.
See section 13.9 for troubleshooting information.