RFL Network Management Software
21. Func 1 output polarity
The Function 1 output polarity can be set to normal or inverted.
22. Func 2 output polarity
The Function 2 output polarity can be set to normal or inverted.
23. Func 3 output polarity
The Function 3 output polarity can be set to normal or inverted.
24. Func 4 output polarity
The Function 4 output polarity can be set to normal or inverted.
25. Func 1 triphold timer (ms)
When a trip is received, it will extend the trip 1 by the time selected. The Function 1 triphold timer can
be set from 0.00ms to 64.00ms in 0.25ms increments. Select the triphold timer value that you want
from the pull down box.
26. Func 2 triphold timer (ms)
When a trip is received, it will extend the trip 2 by the time selected. The Function 2 triphold timer can
be set from 0.00ms to 64.00ms in 0.25ms increments. Select the triphold timer value that you want
from the pull down box.
27. Func 3 triphold timer (ms)
When a trip is received, it will extend the trip 3 by the time selected. The Function 3 triphold timer can
be set from 0.00ms to 64.00ms in 0.25ms increments. Select the triphold timer value that you want
from the pull down box.
28. Func 4 triphold timer (ms)
When a trip is received, it will extend the trip 4 by the time selected. The Function 4 triphold timer can
be set from 0.00ms to 64.00ms in 0.25ms increments. Select the triphold timer value that you want
from the pull down box.
29. Timeslot
The Time Slot can be set from 1-24 for T1 systems and from 1-31 for E1 systems. Click on the desired
time slot in the pull down box to make the selection. In 9508D only E1 internal frame is used.
30. Mode
Mode can be set to 2+2 or 3+1. The first number is the number of uncoded commands and the second
one is the number of coded commands for a total of 4. Thus with operation mode 3+1, commands 1, 2
and 3 are uncoded commands and command 4 is a coded command.
31. Boost
This function is not presently used and should be set to disable.
32. Output enable
When enabled, all outputs are enabled. When disabled, all outputs are disabled.
RFL 9508D UCC
RFL Electronics Inc.
September 7, 2012
4-26