TROUBLESHOOTING
NOTE: If the furnace is equipped with electronic modulation option AG39, AG40, AG41, or AG42,
for additional troubleshooting guidelines.
Table 32. General Troubleshooting
Symptom
Probable Cause
Remedy
A . Venter
motor will not
start
1 . No power to furnace
Turn ON power and check supply fuses or circuit breaker
2 . No 24V power to venter relay
Turn up thermostat and check control transformer output
Check for loose or improper wire connections
3 . Defective venter relay
Replace defective part
4 . Defective motor or capacitor
Replace defective part
B . Pilot will
not light
with venter
operating
1 . Manual valve not open
Open manual valve
2 . Air in gas line
Bleed gas line
3 . Dirt in pilot orifice
Remove pilot orifice and clean with compressed air or solvent
4 . Gas pressure too high or too low
Adjust gas pressure (refer to
Measure and Adjust Manifold (Outlet) Gas
section)
5 . Kinked pilot tubing
Replace tubing
6 . Pilot valve does not open
If 24V power is available at valve, replace valve
7 . No spark
a . Loose wire connections
Ensure that all wires connections are solid
b . Transformer failure
Ensure that 24V power is available
c . Incorrect spark gap
Maintain spark gap at 7/64 inch for RPBL models or 0 .100 inch for SSCBL
models
d . Spark cable shorted to ground
Replace worn or grounded spark cable
e . Spark electrode shorted to ground
Replace pilot if ceramic spark electrode is cracked or grounded
f . Drafts affecting pilot
Ensure that all panels are in place and are tightly secured to prevent drafts
at pilot
g . Ignition control not grounded
Ensure that ignition control is grounded to furnace chassis
h . Faulty ignition controller
If 24V power is available to ignition controller and all other causes have been
eliminated, replace ignition control
8 . Optional lockout device interrupting control
circuit due to above causes
Reset lockout by interrupting control at thermostat
9 . Faulty combustion air proving switch
Replace combustion air proving switch