background image

3.3 Control panel

The control panel is located in the lower 
left of the front panel, refer to instructions 
provided with the control panel.

3.3.1 Limit safety thermostat

The appliance is equipped with a MANUAL 
RESET LIMIT safety thermostat with the 
element positioned on the air supply. It func-
tions to stop the burner if the air becomes 
too hot. It can be restored by pushing the 
restore button, after removing the causes 
that have triggered it.

3.3.2 Fan thermostat

The appliance is equipped with a fan ther-
mostat with the element positioned on the 
air supply. 

Activating the fan max. 60 seconds after the 
burner has started and it stops it approx. 4 
minutes after it has stopped. Thus, prevent-
ing cold air from being released when the 
heater is activated. The thermal energy 
accumulated by the heat exchanger will be 
disposed of before the fan stops.

3.3.2.1 TR safety thermostat

The appliance is equipped with an auto-
matic reset TR safety thermostat with the 
element positioned on the air supply. It has 
the function of stopping the burner if the air 
becomes overheated. Restoring is automatic.

3.4 Controls

For its operation and programming, refer 
to the dedicated instructions, which are 
supplied together with the appliance.

LIMIT thermostat reset button:

Located on the LIMIT thermostat's interface, 
the button will reset the operation of the 
burner after it has stopped due to over-
heating. Before resetting the device please 
verify that the issues have been resolved 
before continuing operation. If confused, 
please contact manufacturer for further 
clarification. 

3.4.1 Ventilation/Heating

Operating cycle in fan only mode:

• Power the appliance
• Turn on the unit in fan only mode

At this point, the fan unit will operate and 
air at ambient temperature will be released.

Operating cycle in heating mode:

• Power the appliance
• Set the room thermostat to desired 

temperature

• Turn on the unit on "heating" mode.

At this point the burner is powered elec-
trically, after the pre-purge function of the 
combustion chamber, the flame will begin 
to ignite. About one minute after the flame 
is ignited, the fan unit starts and warm air 
will be released.

Once the temperature set on the room ther-
mostat has been reached, the burner stops 
and after approx. 4 minutes the fan unit 
will also stop.

The entire cycle is repeated automatically 
each time the temperature drops below the 
value set on the room thermostat.

3.5 Fan speed control

Models 60–300

For all the installations requiring changes 
of static pressure, the air flow should be 
adjusted to the nominal value accordingly.

The pulley installed on the fan motor(s) is 
of the adjustable diameter type. 

The heaters ordinarily come with a median 
transmission ratio, so a nominal value can 
be obtained in installations, as standard.

Begin by checking (when the burner is 
operating on the nominal thermal output) 
the temperature rise between the air outlet 
and inlet temperature and compare with 
the specifications of Table 2 on page 9.

Figure 21. 

Control panel

23

Summary of Contents for FSE 100

Page 1: ...es in force All external wiring must comply with the codes of practice or rules in force in the country of installation Improper installation adjustment alteration service or maintenance can cause pro...

Page 2: ...cluding children with reduced sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person resp...

Page 3: ...ion 14 2 10 Gas Installation connection 14 2 11 Oil Installation connection 14 2 12 Fuel supply 14 2 12 1 Storage tank 15 2 13 Pipe work and fittings 15 2 14 Packaging 18 2 15 Flooring 18 2 16 Electri...

Page 4: ...the instructions of this manual for the consequences of any operations carried out and not specifically provided for or for translations open to misinterpretation The electrical system must feature su...

Page 5: ...en subject to and affected by the ingress of water in any form The heater is not operated at the rating s laid down in the manufacturers technical specifications The heater has not been operated or us...

Page 6: ...level surface made from non combus tible material which is sufficiently robust to withstand the weight of the heater and any ancillary equipment 1 6 General requirements WARNING Unauthorised modifica...

Page 7: ...ety thermostat factory calibration 80 C has the function of interrupting the burner operation in case of abnormal overheating of the air It is automatically reset It shall be correctly calibrated when...

Page 8: ...mm nom FSE 40 600 770 1500 145 130 5 FSE 60 650 950 1650 225 150 6 FSE 75 650 950 1650 245 150 6 FSE 100 800 1200 1900 310 180 7 FSE 145 800 1200 1900 345 180 7 FSE 175 1000 1500 2150 485 205 8 FSE 22...

Page 9: ...V 93 5 93 1 93 6 93 2 94 3 94 5 93 1 94 5 Gross flue gas temperature 2 C 155 155 155 155 140 140 155 140 Combustion chamber pressure Mbar 0 1 0 4 0 5 0 6 0 7 0 5 0 6 1 5 Heat output 1 kW 28 0 38 2 52...

Page 10: ...useful efficiency el max At nominal heating capacity el min At minimum heating capacity el sb In stand by mode F env Envelope loss factor P ign Ignition burner consumption NOx Nitrogen oxide emission...

Page 11: ...ould Be placed on a flat surface capable of bearing its weight Be supported over the entire perimeter of the lower base Be placed on a surface whose deflection and strength is such that it can prevent...

Page 12: ...the system 2 5 Flue gas discharge Flue gas exhaust connection position and example of connection to the flue Condensate discharge fitting is necessary to prevent any condensate that has formed in the...

Page 13: ...the ducts of the air inlet circuit to the side opening the appliance is set up for both right and left connections To change the air inlet side simply swap the grille and blanking panels around To att...

Page 14: ...uel supply WARNING Galvanisedorplasticpipeworkandfittings must not be used See BS 5410 Part 1 The constraints of the application will to a large extent determine whether it is prefer able to use a sin...

Page 15: ...pump is running the oil pressure can be increased sufficiently so as to cause damage to the seals within the pump The return oil should be discharged pref erably through an elbow onto a tank plate si...

Page 16: ...ails 40 175 gravity feed from the bottom of the tank Table 7 Dimensions 1 Gate valve 2 In line filter 3 Pump 4 Relief valve 5 Pressure gauge 6 Pressure reducing valve 7 Return to tank Filler Maximum 4...

Page 17: ...P should not exceed 4 metres to avoid damage to the pump seals The pump suction should not exceed a maximum of 4 metres Beyond this limit gas is released from the oil Oil lines must be completely air...

Page 18: ...mally insulated Where ducting may be subject to deterio ration from exposure to moisture or high humidity material selection and insulation are prime considerations Joints and seams must be airtight a...

Page 19: ...ture C 22 6 22 4 17 17 3 22 2 21 6 20 8 21 8 24 23 2 24 3 24 7 22 21 3 22 7 23 3 Td C 10 2 10 1 6 3 6 4 8 7 8 4 11 5 11 7 13 7 13 2 14 3 14 3 9 1 8 9 6 2 6 7 Smoke number No 0 0 1 1 1 0 0 0 0 0 3 Burn...

Page 20: ...nection of the power supply phase neutral In any case make sure that the direction of rotation of the fans is correct The unit must be connected to an efficient earthing system The manufacturer shall...

Page 21: ...10 M2 Fan motor if present 11 FAN thermostat 12 LM Manual reset safety thermostat 13 TR Automatic reset safety thermostat 14 F1 Fuse 15 BM Single stage burner terminal block 16 BP1 Double stage burne...

Page 22: ...10 M2 Fan motor if present 11 FAN thermostat 12 LM Manual reset safety thermostat 13 TR Automatic reset safety thermostat 14 F1 Fuse 15 BM Single stage burner terminal block 16 BP1 Double stage burne...

Page 23: ...Before resetting the device please verify that the issues have been resolved before continuing operation If confused please contact manufacturer for further clarification 3 4 1 Ventilation Heating Op...

Page 24: ...each motor must be adjusted and its electrical absorption must be checked To change rpm of the fan perform the following operations Relax the belts tension by unloosing the screw 1 Remove the belt 4...

Page 25: ...rance of 10 C Make sure that the manual resetting safety thermostat calibration is correct Check that the temperature near the safety thermostat is correct ambient temperature air temperature Check th...

Page 26: ...pressed on both sides with the hands it should bend between 20 30 mm To manage the tension operate the two belt stretching bolts Thermostat safety check Check functionality of the safety thermostat a...

Page 27: ...able burner via controller by selecting Heat Relay 2 Heat On Heat Auto This is dependent on control type supplied Refer to individual controller operating manual Burner will fire and establish within...

Page 28: ...7 Electrode 3008930 3008931 3008930 3008931 3008930 3008931 3008931 3008932 Probe 3007987 3007988 3007988 3007988 3007988 3007988 Propane conversion kit 30 00 882 30 00 884 30 00 884 30 00 886 30 00 8...

Page 29: ...Notes 29...

Page 30: ...Notes 30...

Page 31: ...Notes 31...

Page 32: ...olmore Circus Queensway Birmingham West Midlands B4 6AT AFFIX AGENTS DETAILS HERE This document replaces the previous Manual Part No Reznor FSE EN Oct 18 D301160 Issue B Current full Part No Reznor FS...

Reviews: