Revision 2.6
Page 21 of 53
Intuitive Mercury 6-5M Controller with TDB
www.resourcedm.com
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
I/O Objects & Properties
Analogue Input
Icon
Properties
*Probe types: -
PT1000
2K
470R
700R
3K
2K25
100K
5K
6K
10K
10K Type 2 (USA)
Raw*
Custom** Define
*
If Probe type “Raw” is selected then no resistance to temperature conversion will take place, value displayed will be the probe’s resistance
value in ohms.
Note: If input is left open circuit the block will give a very high reading i.e. 1999999. If the input is short circuited the block will give a very low
reading i.e. 7.3
Used in conjunction with an “In Range Block” this gives the equivalent feature of a digital input behaving like “Plant N/O and N/C”
**If an analog input has been configured to use a Custom profile then to select and use one of the preset probe types e.g. PT1000, the analog
input must be deleted and reinserted into the program.
Fixed inputs are the Intuitive Mercury TDB Controller
built in Inputs.
Input:
Select the input from the drop-down menu.
If a probe has been selected, select the probe type*.