Mercury 2 & Intuitive Mobile Controller User Guide
www.resourcedm.com
P-45
Def Min Time
00:00 to 99:00
01:00
mm:ss
05:00
05:00
P-46
Def Max Time
00:00 to 99:00
01:00
mm:ss
30:00
30:00
P-47
Drain Down
00:00 to 24:00
00:15
mm:ss
01:30
00:30
P-48
Recovery Time
00:00 to 99:00
01:00
mm:ss
30:00
30:00
P-89
Pump Down Time
00:00 to 99:00
01:00
mm:ss
00:00
00:00
P-86
Fan Delay mode
0 = Time 1 = Temp
1
0
0
P-49
Fan Delay Time
00:00 to 99:00
01:00
mm:ss
00:00
00:00
P-88
Fan Delay Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-50
Fans In Defrost
0 (Off), 1 (On)
On
On
P-91
Defrost Type (Integral)
0 = Elec. 1 = Gas.
2 = Elec CIn
0
0
P-94
Defrost Hold
0 (Off), 1 (On)
Off
Off
P-95
Defrost Skip
0 (Off), 1 (On)
Off
Off
P-96
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss
12:00
12:00
P-60
Lights Mode
0 (Local), 1 (Remote),
2 (Man Off), 3(Man On)
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
dFLt
Restore defaults
Parameter Descriptions
Number
Parameter
Description
P-01
Cut-in Temp
Temperature at which the lead compressor will switch on.
P-02
Diff
Differential temperature below the cut-in temperature. The lead compressor switches off when below this
temperature
P-03
Control Weight
Percentage of the Air-On temperature that is used to calculate the control temp. The remaining
percentage will be used on the Air-Off temperature
Example, P-03 set to 30%
Control temp = 30% Air-on + 70% Air-off
P-04
Display Weight
As above only applied to the display temperature
P-05
Lag Comp Delay
Delay before the second compressor is switched on if the temperature is still above set-point.
Note
– The lead and lag compressors swap after each defrost to even the run times.
P-06
Anti SC Time
Allows the user to set the compressor for a given number of starts/hour
P-07
Lag Cut Out Diff
Diff below the Cut-In Temp the lag compressor switches off.
Single Compressor Operation
To disable compressor B operation and use only a single compressor for control set parameter P-07 to 0.
This will allow the controller work with just one compressor (A) and ignore compressor B.
P-85
Key-switch Mode
Allows the keys switch to be: -
Single turn for case off (Case off mode)
Single turn for Fans only (Fans Mode)
Single turn for case off, double turn for fans only (Toggle mode)
P-87
Control Probe type
Switches between using the air-on probe and the Logging probe. Note the control and display
temperature will still be a derivative of the weighted
Average of the control probe + Air-off probe
P-90
Resistor Case Off
Turns on/off the switched resistor case off function
P-92
Fans temperature
mode
Allows the user to set the fans to turn off when: -
A pre-determined temperature is reached (P93)
When an over-temperature alarm is present
When either P93 is reached or an OT alarm is present
P-93
Fans Off Temperature
Temperature for the above (P92) operation.
Note
the defrost termination probe is the source of the
temperature reading used in this feature. If the defrost termination probe isn’t fitted then a similar process
to P-44 is used.