Warning 

 
 
 
 
 
 

Please Note 

The specifications of the product detailed on this 
Set-Up  Guide  may  change  without  notice.  RDM 
Ltd. shall not be liable for errors or for incidental 
or consequential damages, directly and indirectly, 
in connection with the furnishing, performance or 
misuse of this product or document.

 

Ensure that all power is 
switched off before   
installing or maintaining 
this product 

Mercury 2 & Intuitive Mobile Controller User Guide

 

 

www.resourcedm.com 

Input and Output Allocation Tables 

 

The following tables indicate; on a controller type basis, the functions of the inputs and outputs. Also shown are the digital inputs that are 
derived by switching in a fixed value resistor across the input. 
 
 

Input / Output allocation table 

 

TYPE 

Integral Case 

Types 1&2 

Alarm  

Action 

Plant Input 

(Switched Resistors) 

Input 1 

Air on Temperature 

Yes 

  

Input 2 

Air off Temperature 

Yes 

  

Input 3 

Compressor A Discharge Temperature 

Yes 

Plant fault 1 or External Defrost Input ** 

Input 4 

Compressor B Discharge Temperature 

Yes 

Case Clean Switch 

Input 5 

Defrost Termination or Monitor probe (if used) 

Conditional* 

Plant fault 2 

Input 6 

Logging Probe (If fitted) 

Conditional* 

  

Relay 1 

Compressor A  

N/A 

  

Relay 2 

Fans  

N/A 

  

Relay 3 

Lights/Alarm Relay 

N/A 

  

Relay 4 

Compressor B  

N/A 

  

Relay 5 

Defrost Heater 

N/A 

  

 

* Alarm on monitor probe only if used 
** Defrost type must be set to remote in parameters. 

 

Switched Resistor Values 

For PT1000 probes use 820 Ohm switched resistors. For NTC2K, NTC2K25 and 3K probes use 590 Ohm switched resistors. For 5K and 
6K use 1K Ohm switched resistors. For NTC10K probes use 2k7 Ohm switched resistors. For NTC10K(2) probes use 2k2 Ohm switched 
resistors. The resistors used must have a tolerance of 1% or better and the resistor must have a power rating of 0.25W. For improved 
accuracy whilst using switched resistors RDM recommend resistors with 0.1% accuracy are used. Note the switched resistor features will 

not 

function when using 470R or 700R probes. When a resistor is switched across the appropriate input it signals to the Mercury to 

enable the switched resistor function described for that input whilst still recording the probe temperature on the input. 
 
Temperature range for all probe types is -49

o

C to +127

o

C

 

for probe inputs which do not have a secondary function (switched resistors). 

Inputs which have a secondary function are restricted to -42

o

C to +60

o

C. If the full temperature range is required on all inputs and no 

switch resistor features are needed then please see Switch Resistor parameter P-19 
 
Note: switched resistors will operate in LT (Low Temperature) and HT (High Temperature) applications using PT1000, NTC2K or 
NTC2K25 probe types only. For all other probe types the switched resistor inputs will work in HT applications only. 

 
 
Setting up the controller 

 

Access to the controller can be achieved several ways 

 

Through the front mounted buttons 

 

Direct access by PC into the side comms port. This requires the Communicator software package available free on the RDM 
website 

 

Through legacy front end panels on 485 networks 

 

Through the RDM Data Manager. 

 

Across an IP network. (Current controller IP address required) 

 
 
Setup through front buttons 
 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 

 

To enter setup mode, hold the Enter and Down 
buttons together for approximately 3 seconds until 
the message “Ent” appears on the display. Now 
press the Enter button again to enter the function 
menu. IO will be displayed. Scroll up or down to go 
through the list. 

ENTER 

UP 

DOWN 

DEFROST 

Summary of Contents for PR0710-MOB

Page 1: ...rce Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 sales resourcedm com US OFFICE Resource Data Management Inc 100 North Sixth Stree...

Page 2: ...e achieved at the network front end 8 Unit Set view temperature unit and Probe type 8 Display 9 Parameter Tables 9 Parameter Descriptions 10 Relay State and functional operation 12 Relay and screen st...

Page 3: ...Ensure that all power is switched off before installing or maintaining this product Mercury 2 Intuitive Mobile Controller User Guide www resourcedm com Fixing 19 Dimensions 20 Intuitive Mercury Mount...

Page 4: ...B Intuitive Mercury Single or Twin Compressor Controller integral display PR0750 MOB Intuitive Mercury Single or Twin Compressor Controller remote display PR0760 MOB Intuitive Mercury Single or Twin C...

Page 5: ...tuitive Mercury display is Green in colour when lit Connections Mercury Mk2 6 5E and 6 5M Enter Up Down Defrost Note Function keys illuminate when pressed illumination is turned off 20 seconds after t...

Page 6: ...scription RS232 IP IP Interface RS485 RS485 Interface IP Network Card PR0770 Rotary Address Switches Network Collision LED Network Activity LED Network Expansion Port The Intuitive Mercury is supplied...

Page 7: ...0 25W For improved accuracy whilst using switched resistors RDM recommend resistors with 0 1 accuracy are used Note the switched resistor features will not function when using 470R or 700R probes Whe...

Page 8: ...meter list below to find what parameter number corresponds to which actual parameter Pressing the Enter button will show the current value of the selected parameter Press Up or Down to modify the valu...

Page 9: ...to 86 0 1 Deg 10 14 8 46 4 P 15 Probe 5 Select 0 Defrost 1 Monitor 1 0 0 P 16 Relay 3 Mode 0 Lights 1 Alarm 1 0 0 P 29 Probe 3 Resistor function 0 Plant fault 1 External defrost 1 0 0 P 18 Service In...

Page 10: ...scription P 01 Cut in Temp Temperature at which the lead compressor will switch on P 02 Diff Differential temperature below the cut in temperature The lead compressor switches off when below this temp...

Page 11: ...harge probe exceeds this value and P 30 and P 31 are set to ON then the relevant compressor will be disabled P 33 Discharge Stop Differential This is the differential below the discharge stop value th...

Page 12: ...remote command from the front end starts the recovery process P 95 Defrost Skip Allows user to enable disable defrost skip This feature allows the controller to skip defrosts If the current defrost t...

Page 13: ...ed as on during defrost Network Configuration The final section to setup is the network address In all instances this must be done before the controller is plugged into the site network The controller...

Page 14: ...mation if the network type is set to Genus compatible Press the Enter button to execute the command Up or Down buttons to cancel If the network type is not set to Genus compatible then the ClrA messag...

Page 15: ...255 192 0 18 255 192 0 0 10 255 255 255 128 25 255 255 128 0 17 255 128 0 0 09 255 255 255 0 24 255 255 0 0 16 255 0 0 0 08 Mercury Switch Please refer to the Mercury Switch user guide which can be o...

Page 16: ...ton presses The top bar of the left hand segment will be lit when the maximum temperature is being displayed The bottom bar of the left hand segment will be lit when the minimum temperature is being d...

Page 17: ...Lights Only state if the current state is not Lights Only If the current state is Lights Only then the controller will change to the Normal state Selecting this option will exit the setup menu automat...

Page 18: ...no requirement for forced cooling ventilation There is no requirement for forced cooling ventilation Class 2 Insulation No protective Earth is required and none should be fitted No protective Earth is...

Page 19: ...Input type Selectable See Units Comms RS232 with flow control Switched Resistor Example Wiring Installation Panel Cut out and Clearances Mercury Mk2 Flush mount controller Dimensions Mercury Mk2 Fixin...

Page 20: ...ch clip until it clicks to remove the controller Each clip has a mounting hole to provide an alternative fixing mechanism to DIN mounting Cleaning Do not wet the controller when cleaning Clean the fro...