For the use of a further heat source (e.g. solid fuel boiler),
one or two thermostat functions can be activated additio-
nally to the differential function, in order to allocate a mi-
nimum temperature to the boiler or to limit the maximum
tank temperature.
In order to control a circulation pump, it might be enough
to activate the timer. With the aid of the 21 time frames,
the
relay can be switched individually in the morning, at noon
and in the evening. This process can be further optimized by
activating a thermostat function so that - with a sensor in the
circulation line- control is also temperature-dependent.
S3
R3
minimum temperature limitation for the boiler
maximum temperature limitation for the tank
arrangement/Options/timer 1
........................................................change setting to “Yes”
arrangement/adj. values/timer 1/t1-on
.......................................change value to “06:00”
arrangement/adj. values/timer 1/t1-off
.....................................change value to “08:00”
arrangement/adj. values/timer 1/t2-on
......................................change value to “11:30”
arrangement/adj. values/timer 1/t2-off
....................................change value to “13:30”
arrangement/adj. values/timer 1/t3-on
......................................change value to “18:00”
arrangement/adj. values/timer 1/t3-off
....................................change value to “21:00”
arrangement/Options/Thermo. 1
...................................................change setting to “Yes”
arrangement/adj. values/Th1 on
.................................................change value to “120”
Arrangement/adj. values/Th1 off
................................................change value to “130”
S5
S6
R4
D
T6:
S5>S6
Th3:
S5
Th4:
S6
R4
Th1:
S3
Timer 1
R3
arrangement/Options/
D
T-Func6
...........change setting to “Yes”
arrangement/Options/Thermo.3
...........change setting to “Yes”
arrangement/adj. values/Th3 on
........change value to “140”
arrangement/adj. values/Th3 off
......change value to “130”
arrangement/Options/Thermo.4
...........change setting to “Yes”
arrangement/adj. values/Th4 on
.......change value to “136”
arrangement/adj. values/Th4 off
......change value to “140”
D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.mon
us.ind
d
13
|