5. Troubleshooting
fuse T4A
Control lamp off
Control lamp flashes red
Sensor defect. An error code instead of
a temperature is displayed in the sensor
display channel.
- 888.8
888.8
Cable broken.
Check cable.
Short circuit.
Check cable.
Disconnected Pt1000 temperature sen-
sors can be checked with an ohmeter. In
the following table, the resistance values
with the corresponding temperatures are
shown.
spare fuse T4A
In the case of an error, a message is shown on the display
of the controller:
operating control
lamp
°F
Ω
°F
Ω
14
961
131 1213
23
980
140 1232
32
1000
149 1252
41
1019
158 1271
50
1039
167 1290
59
1058
176 1309
68
1078
185 1328
77
1097
194 1347
86
1117
203 1366
95
1136
212 1385
104 1155
221 1404
113 1175
230 1423
122 1194
239 1442
resistance of the
Pt1000 sensors
D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.mon
us.ind
d
|
40
Check the power supply. Is it disconnected?
no
The fuse of the controller
could be blown. It can be
replaced after the front
cover has been removed
(spare fuse is enclosed in
the fuse holder).
yes
Check the supply line and
reconnect it.